ZC702 EVALUATION KIT
QUICK START GUIDE
STEP 8IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIISTEP 7IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
STEP 9IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
Initialize Configuration
Press SW1 POR_B to reinitialize the configuration for 
the ZC702 board.
Terminal Display
After the ZC702 board is configured, the text shown below appears in the terminal emulator window. Type the number 
or the letter associated with a listed option to run a test application. For example, type 2 to run the LED Test 
application.
Note: DIP switches (SW15-1 and -2) 
are tied in parallel to push buttons 13 
and 14, respectively. Either use the 
DIP switches, or set SW15-1 and -2 
to OFF and use push buttons 13 and 
14.
3
Set Up Terminal Emulator: Serial Setup
Select the same COM port assigned in Step 5 and set the 
Baud rate to 115200, the Data to 8 bit, the Parity to 
none, Stop to 1 Bit and Flow control to none.  
Click OK to save the settings.