C60 Users Manual
Page 7
Uninterrupble Power Supply
Specicaons
MODEL NUMBER
C60‐800 C60i‐800
INPUT
Capacity 800VA (480W)
Nominal voltage 120VAC 230VAC
Voltage range 80–135VAC ± 5% 175–254VAC
Frequency range 55–65Hz at 60Hz ± 1Hz 45–55Hz at 50Hz ± 1Hz
Surge protecon 158 J
AC power cord 6 , IEC C13 to 5–15P IEC C14 inlet only
OUTPUT
Voltage (line mode) 80–135VAC ± 5% 175–254VAC
Voltage (baery mode) 120VAC ± 10% 230VAC ± 10%
Voltage regulaon ± 2%
Frequency (line mode) 55–65Hz at 60Hz ± 1Hz 45–55Hz at 50Hz ± 1Hz
Frequency (baery mode) 60Hz ± 1Hz 50Hz ± 1Hz
Waveform Sine wave (normal), simulated sine wave (baery mode)
Transfer me 2–6 ms
Outlets (2) NEMA 5–15R (2) IEC C13
Overload capacity 110% +20% / ‐10% for 5 min; 120% +20% / ‐10% immediately o
Eciency > 95%
BATTERY
UPS baery type (1) 12V 9AH / 12VDC
UPS charge current 1A maximum
Recharge me 8 hours to 90% capacity
PHYSICAL
Dimensions (W x D x H) 4.0 x 13.0 x 5.7 in
Weight 7.5 lbs
ENVIRONMENT
Temperature 32–104°F (0–40°C)
Humidity 0–90%
Altude 11,500  above sea level
INDICATORS &
Line mode Green LED illuminated
ALARMS Baery mode Green LED ashing every 10 sec
Baery low Green LED ashing every 1 sec
Fault mode O
Audible alarm
Baery mode ‐ every 10 sec; low baery ‐ every 1 sec; overload ‐ ever 0.5 sec;
fault ‐ constant alarm
APPROVALS UL 1778, FCC Class A, RoHS S‐Mark, EN62040‐1, EN62040‐2, RoHs
WARRANTY 3 years electronics, 3 years baery (USA and Canada)