EasyManua.ls Logo

Yale PR3301 - User Manual

Yale PR3301
6 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Installation Instructions
80-9303-2209-010 (04-06)
An incorrectly installed or improperly
adjusted door closer can cause
property damage or personal injury.
These instructions should be followed
to avoid the possibility of
misapplication or misadjustment.
CAUTION
CAUTION
Standard Frame Installation
Closer mounts on opposite to hinge (push) side of door. PR3301 Parallel Rigid Non Hold Open arm illustrated. Slim Line Cover shown.
See Pages 3 and 4
Right Hand Door RH
Left Hand Reverse LHR
Left Hand Door LH
Right Hand Reverse RHR
Additional Closer Options:
- “DL” indicates Delayed Action closing.
- “H” indicates Hold-Open function components are handed.
- “T” indicates Thumbturn actuated Holder-Stop control.
Optional Accessories:
- 3148 Dropplate
- 293L, 293S, 890, 891 Soffit Plate Accessories.
NOTE: For special applications a separate door and frame preparation template is packed with these instructions. In those
cases, use this instruction sheet for installation sequence and closer adjustments only.
Narrow Frame Installation
Closer mounts on opposite to hinge (push) side of door. CLP3501 CloserPlus arm illustrated. Full Cover shown.
890 and 891 accessories required for this application (supplied separately).
See Pages 3 and 4
Right Hand Door RH
Left Hand Reverse LHR
Left Hand Door LH
Right Hand Reverse RHR
Flush Partition Installation
Closer mounts on opposite to hinge (push) side of door. CLP3101T CloserPlus arm with Thumbturn Hold Open illustrated.
Closer Cover not shown. 293L accessory required for this application (supplied separately).
See Pages 3 and 4
Right Hand Door RH
Left Hand Reverse LHR
Left Hand Door LH
Right Hand Reverse RHR
Hinge Edge
of Door
Hinge Edge
of Door
Hinge Edge
of Door
Hinge Edge
of Door
Hinge
Edge
of Door
Hinge
Edge
of Door
Parallel Rigid Arm Door Closers (PR)
Holder-Stop Door Closers
Hold-Open Door Closers
Model Numbers Included:
PR3301/ PR330X
PR3311/ PR331X
3321(T) / 332X(T)
Note ‘X’ Designates Size 2, 3, 4, 5, or 6
PR3501/ PR350X
PR3511/ PR351X
3521(T) / 352X(T)
Question and Answer IconNeed help?

Do you have a question about the Yale PR3301 and is the answer not in the manual?

Summary

Standard Frame Installation

Narrow Frame Installation

Flush Partition Installation

Preparation for Fasteners

Main Arm Installation Instructions

3148 Drop Plate Mounting Holes

Thumbturn Hold-Open Feature

Friction Hold-Open Feature

Unit Adjustment

Closing Power Adjustment

Adjusts the closer's spring power using a hex key for proper closing action.

Control Valve Adjustments

Details how to adjust valves for sweep, latch, and optional delay ranges.

Closing Speed Controls

Explains adjustment of Sweep, Latch, and Delay valves for door closing speed.

Opening Cycle and Backcheck

Controls cushioning strength in the opening range, never close completely.

Cover Mounting

Instructions for installing various types of covers onto the door closer.

Summary

Standard Frame Installation

Narrow Frame Installation

Flush Partition Installation

Preparation for Fasteners

Main Arm Installation Instructions

3148 Drop Plate Mounting Holes

Thumbturn Hold-Open Feature

Friction Hold-Open Feature

Unit Adjustment

Closing Power Adjustment

Adjusts the closer's spring power using a hex key for proper closing action.

Control Valve Adjustments

Details how to adjust valves for sweep, latch, and optional delay ranges.

Closing Speed Controls

Explains adjustment of Sweep, Latch, and Delay valves for door closing speed.

Opening Cycle and Backcheck

Controls cushioning strength in the opening range, never close completely.

Cover Mounting

Instructions for installing various types of covers onto the door closer.

Overview

This manual describes the installation and adjustment of Yale Parallel Rigid Arm Door Closers (PR), Holder-Stop Door Closers, and Hold-Open Door Closers.

Function Description:

The Yale door closers are designed to control the closing motion of a door, providing various functionalities such as standard closing, holding the door open at a desired angle, or stopping the door at a specific point. They are suitable for different door and frame configurations, including standard frames, narrow frames, and flush partitions. The closers are available with several options, including Delayed Action (DL) for slower closing, Handed Hold-Open (H) components, and Thumbturn actuated Holder-Stop (T) control.

Important Technical Specifications:

The closers are available in various model numbers, including PR3301/PR330X, PR3311/PR331X, PR3501/PR350X, PR3511/PR351X, 3321(T)/332X(T), and 3521(T)/352X(T). The 'X' in the model numbers designates sizes 2, 3, 4, 5, or 6.

Components:

The main components of the door closer include:

  • Closer Body: Contains the internal mechanisms for closing control, including the backcheck valve, delay valve (optional), latch valve, and sweep valve.
  • Power Adjustment Shaft: Used to adjust the closing power.
  • Soffit Plate: A mounting plate for the frame.
  • Closer Arm: Consists of a main arm and a secondary arm. Different arm options are available:
    • PR Arm Assembly: Standard arm with a riveted elbow.
    • CLP Arm Assembly Stop only: Includes a removable stop and a riveted elbow.
    • PR Hold Open Arm Assembly: Features a friction hold-open nut and a riveted elbow.
    • CLP Arm Assembly with Thumbturn: Includes a thumbturn hold-open mechanism, a removable stop, and a riveted elbow.
  • Cover Options:
    • Standard 3501 Full Plastic Cover: With insert cutouts.
    • Standard 3301 Slim Line Plastic Cover: With a pinion cap.
    • Optional 3501M Full Metal Cover: Uses cover clips and screws.
    • Optional Architectural Metal Cover: Requires standoffs and screws.
    • Optional Architectural Plastic Cover: Uses standoffs and screws.

Fastener Preparation:

  • Self-Drilling Screw:
    • Aluminum or Metal: No drill required.
    • Wood: 3/16" (4.30 mm) drill size. (Note: Wood doors MUST be pre-drilled when using Self-Drilling Screws.)
  • 1/4" - 20 machine screw:
    • Metal: Drill #7 (0.201" dia.), Tap 1/4" - 20.
  • Sleeve nuts and bolts:
    • Hollow Metal: 9/32" (7 mm) through; 3/8" (9.5 mm) door face opposite to closer.
    • Aluminum or Wood: 3/8" (9.5 mm) through.
  • Through-bolts and grommet-nuts:
    • All: 9/32" (7 mm); 3/8" (9.5 mm) dia. x 3/8" (9.5 mm) deep on door opposite to closer.

Installation Dimensions:

Detailed charts are provided for installation dimensions (A and B) based on the desired angle of opening (85° to 180°) and hinge type (Butt Hinges or Offset Pivots, Center Pivots).

Usage Features:

  • Power Adjustment: The closing power can be adjusted using a 1/8" hex wrench on the power adjustment shaft. Turning clockwise increases power, while counter-clockwise decreases it. A maximum of 20 turns (360°) is allowed. The closer is shipped set at mid-power.
  • Closing Speed Controls:
    • Sweep Range (Valve 'S'): Controls the speed of the door's main closing arc.
    • Latch Range (Valve 'L'): Controls the speed of the door's final closing phase (latch speed).
    • Delay Range (Valve 'D', optional): Controls the duration of delayed action closing.
    • Caution: Do not back valves out of the closer completely, as this will result in a leak.
  • Backcheck Control: The backcheck valve controls the strength of cushioning in the backcheck range, preventing the door from slamming open. It is not intended to provide a positive stop and should NEVER be completely closed.
  • Hold-Open Features:
    • Thumbturn Hold-Open: Controlled by a knob on the arm. Turning clockwise engages and increases hold-open force; counter-clockwise reduces force and disengages the mechanism.
    • Friction Hold-Open: Holds the door open at the desired angle by tightening a holder-adjustment-nut (wrench supplied or 1" box/open end wrench).

Maintenance Features:

  • The manual emphasizes proper adjustment of the sweep and latch valves for optimal closing action.
  • Regular checks of the power adjustment and valve settings are implied for continued performance.
  • The instructions guide users on how to install and adjust the closer, which are key aspects of maintenance to ensure longevity and proper function.
  • Cover installation instructions are provided for various cover types, which protect the internal mechanisms.

Important Notes:

  • An incorrectly installed or improperly adjusted door closer can cause property damage or personal injury.
  • For special applications, a separate door and frame preparation template is packed with the instructions.
  • Architectural Covers CAN NOT be used for doors swinging over 120° using parallel mount.
  • The closing speed time should be adjusted to between 4 to 7 seconds from 90°, especially for handicapped, elderly, or small children.