G.F.C.I. receptacle test
1. Start the engine.
2. Press the test button, then check the position of
the reset button.
1 Test button
2 Reset button
3. If G.F.C.I. operation is correct, push in the reset
button.
If the G.F.C.I. operates incorrectly, consult a
Yamaha dealer.
Do not operate the generator with a faulty G.F.C.I.
circuit. Electric shock could occur. Have the gen-
erator repaired by a qualified mechanic.
G.F.C.I. Reset
G.F.C.I. Receptacle
Button Position
Operation
after Test
3 Pop Out Correct
4 Stay In Incorrect