2 - 1 RS-485 Connection
3
Chapter 2. WIRING
An example of connection methods in such a case is shown below.
Connect terminating resistors of 150±5%, 1/2W min. at each end of the trans-
mission line.
Terminal block is required for the CMQ-V series because of the connector type
connection.
The cable to the terminal block from the CMQ-V series must be as short as pos-
sible.
The FG grounding must not be made at the both shielded wire ends but only at
one location.
Yamatake’s CMC10L001A000 can be used as a converter of the host station.
Handling Precautions
Be sure to connect SG terminals each other. Failure to do so might cause
unstable communications.
FG
FG
CMQ-V Series
(slave station)
CMQ-V Series
(slave station)
CMQ-V Series
(slave station)
CMQ-V Series
(slave station)
Terminating
resistor
Terminating
resistor
Shielded cable
Shielded cable
Terminal
block
Terminal
block
DA
DB
SG
DA
DB
SG
7
8
9
7
8
9
DA
DB
SG
FG
Master station
DA
DB
SG
DA
DB
SG
7
8
9
7
8
9