EasyManuals Logo

Yamatake Azbil CMQ-V Series User Manual

Default Icon
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
2 - 1 RS-485 Connection
3
Chapter 2. WIRING
An example of connection methods in such a case is shown below.
Connect terminating resistors of 150±5%, 1/2W min. at each end of the trans-
mission line.
Terminal block is required for the CMQ-V series because of the connector type
connection.
The cable to the terminal block from the CMQ-V series must be as short as pos-
sible.
The FG grounding must not be made at the both shielded wire ends but only at
one location.
Yamatake’s CMC10L001A000 can be used as a converter of the host station.
Handling Precautions
Be sure to connect SG terminals each other. Failure to do so might cause
unstable communications.
FG
FG
CMQ-V Series
(slave station)
CMQ-V Series
(slave station)
CMQ-V Series
(slave station)
CMQ-V Series
(slave station)
Terminating
resistor
Terminating
resistor
Shielded cable
Shielded cable
Terminal
block
Terminal
block
DA
DB
SG
DA
DB
SG
7
8
9
7
8
9
DA
DB
SG
FG
Master station
DA
DB
SG
DA
DB
SG
7
8
9
7
8
9

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Yamatake Azbil CMQ-V Series and is the answer not in the manual?

Yamatake Azbil CMQ-V Series Specifications

General IconGeneral
BrandYamatake
ModelAzbil CMQ-V Series
CategoryController
LanguageEnglish

Related product manuals