5 Installation Procedure
YASKAWA ELECTRIC SIEP C730600 59A V1000 Option Modbus TCP/IP Technical Manual 15
Table 6 Ground Wire Selection
5. For IP20/Open-Chassis models, go to Step 9. on page 16.
6. For IP20/NEMA Type 1 enclosure models CIMR-VAF, loosen the screw on the front of the NEMA
Type 1 terminal cover and remove it from the drive. Refer to Figure 8 for details.
Refer to Figure 9 for drive models CIMR-VBA0006F to BA0018F, 2A0008F to 2A0069F, and 4A0001F to
4A0038F, which require removing the plastic terminal cover prior to removing the NEMA Type 1 terminal cover.
Note: Installing the option on an IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection while maintaining IP20
conformity.
Figure 8
Figure 8 Remove the NEMA Type 1 Terminal Cover (CIMR-VBA0001F to BA0003F, 2A0001F to 2A0006F)
Figure 9
Figure 9 Remove the Terminal Cover on an IP20/NEMA Type 1 Drive
(Models CIMR-VBA0006F to BA0018F; 2A0008F to 2A0069F; 4A0001F to 4A0038F)
Ground Wire Length
mm (in)
Drive Model
CIMR-V
Single-Phase
200 V Class
Three-Phase
200 V Class
Three-Phase
400 V Class
150 (5.9)
BA0001
BA0002
BA0003
2A0001
2A0002
2A0004
2A0006
–
200 (7.9)
BA0006
BA0010
BA0012
BA0018
2A0010
2A0012
2A0020
4A0001
4A0002
4A0004
4A0005
4A0007
4A0009
4A0011
250 (9.8) –
2A0030
2A0040
4A0018
4A0023
400 (15.7) –
2A0056
2A0069
4A0031
4A0038