6 Related Drive Parameters
YASKAWA ELECTRIC SIEP C730600 59A V1000 Option Modbus TCP/IP Technical Manual 21
F7-06
(3EA)
<5>
Subnet Mask 2
Sets the static/fixed Subnet Mask.
Parameter F7-06 sets the second most significant octet.
Default: 255
Range: 0 to 255
F7-07
(3EB)
<5>
Subnet Mask 3
Sets the static/fixed Subnet Mask.
Parameter F7-07 sets the third most significant octet.
Default: 255
Range: 0 to 255
F7-08
(3EC)
<5>
Subnet Mask 4
Sets the static/fixed Subnet Mask.
Parameter F7-08 sets the fourth most significant octet.
Default: 0
Range: 0 to 255
F7-09
(3ED)
<5>
Gateway Address 1
Sets the static/fixed Gateway address.
Parameter F7-09 sets the most significant octet.
Default: 192
Range: 0 to 255
F7-10
(3EE)
<5>
Gateway Address 2
Sets the static/fixed Gateway address.
Parameter F7-10 sets the second most significant octet.
Default: 168
Range: 0 to 255
F7-11
(3EF)
<5>
Gateway Address 3
Sets the static/fixed Gateway address.
Parameter F7-11 sets the third most significant octet.
Default: 1
Range: 0 to 255
F7-12
(3E0)
<5>
Gateway Address 4
Sets the static/fixed Gateway address.
Parameter F7-12 sets the fourth most significant octet.
Default: 1
Range: 0 to 255
F7-13
(3F1)
Address Mode at Startup
Selects how the option address is set.
0: Static
1: BOOTP
2: DHCP
Default: 2
Range: 0 to 2
F7-14
(3F2)
Duplex Mode Selection
Selects duplex mode setting.
0: Half duplex forced
1: Auto-negotiate duplex mode and communication speed
2: Full duplex forced
Default:
<6>
Range: 0 to 2
F7-15
(3F3)
<7>
Communication Speed Selection
Sets the communication speed.
0: 10 Mbps (Available only with drive software version PRG: 1012 to
1015)
1: 10 Mbps
100: 100 Mbps
Default:
<8>
Range: <8>
F7-16
(3F4)
Communication Loss Time-out
Sets the time-out value for communication loss detection in tenths of a
second. A value of 0 disables the connection time-out.
Example: An entered value of 100 represents 10.0 seconds.
Default: 0
Min.: 0
Max.: 300
H5-11
(43C)
Communications ENTER Function
Selection
Select the function for the ENTER command that saves parameter data to
the drive.
0: Parameter changes are activated when ENTER command is written
1: Parameter changes are activated immediately without use of ENTER
command
Default: 1
Range: 0, 1
<1> To start and stop the drive with the option master device using serial communications, set b1-02 to 3. To control the drive frequency reference
via the master device, set b1-01 to 3.
<2> If F6-01 is set to 3, the drive will continue to operate when a fault is detected. Take safety measures, such as installing an emergency stop
switch.
<3> Cycle power for setting changes to take effect.
<4> If F7-13 is set to 0, then all IP Addresses (F7-01 to F7-04) must be unique.
<5> Set F7-01 to F7-12 when F7-13 is set to 0.
<6> Default setting differs by drive software version.
1012 to 1015: 0
≥1016: 1
<7> Set F7-15 when F7-14 is set to 0 or 2.
<8> The setting values differ by drive software version.
1012 to 1015
Default: 0
Range: 0, 10, 100
≥1016
Default: 10
Range: 10, 100
No.
(Addr. H)
Name Description Values
Modbus_conditional_E.fm 21 ページ 2012年3月7日 水曜日 午前11時31分