7 Modbus TCP/IP Messaging
YASKAWA ELECTRIC SIEP C730600 59A V1000 Option Modbus TCP/IP Technical Manual 31
Modbus TCP/IP Exception Codes
An error may occur when the option responds to a command. The response message will contain one of the Error Codes
defined in Table 3 7.
Table 37 Modbus TCP/IP Exception Codes
Control Connection Timeout
The option has a safety feature that declares a fault if communications between the master and drive is lost after the
master commanded the drive to run.
A controlled connection is defined as one in which a master commands the drive by writing to register 01H. After this
write, the option will begin a timer. The timer will be reset upon subsequent writes to register 01H. If the timer exceeds
the value programmed in drive parameter F7-16, then the option will declare a BUS ERROR to the drive. A value of 0 in
F7-16 means that the timeout is disabled.
The drive reaction to a BUS ERROR is programmable through drive parameter F6-01.
Error Code (H) Error Name and Cause
01
Function Code Error.
Attempted to set a function code from a PLC other than 03, 06, 10, or 17 (H).
02
Register Number Error.
A register number specified in the command message does not exist.
03
Bit Count Error.
Invalid command message quantity
In a write message, the value for write byte count does not match twice the value of the stated quantity of registers to
write
21
Data Setting Error.
Control data or parameter write data is outside the allowable setting range
Attempted to write a contradictory parameter setting
22
Write Mode Error.
Attempted to write while the drive was operating to a parameter that cannot be written during run
During an EEPROM data error (CPF06), the master attempted to write to parameter other than A1-00 to -05, E1-03, or
o2-04
Attempted to write to a read-only register
23
DC Bus Undervoltage Write Error.
Attempted to write from the master during an undervoltage fault (Uv1)
Attempted to execute an Enter command during Uv1
24
Write Error During Parameter Process.
Master attempted writing to the drive while the drive was processing parameter data.