1
:
Remove the insulator from the tips of wires to the length shown in
“
Wire
Stripping Length.
”
*
2
:
When using wire with a gauge over
30
mm
2
, tighten to a tightening torque of
4
.
1
to
4
.
5
N
・
m.
*
3
:
Terminals - and
+
have two screws. Recommended Gauge means the wire
gauge of one terminal.
*
4
:
Use cables in the range of applicable gauges to meet the IP
20
protective level.
*
5
:
A junction terminal is required when connecting a braking unit
(
CDBR
-
series
)
or a braking resistor unit
(
LKEB
-
series
)
.
Note
:
The recommended wire gauges based on drive continuous current ratings
using
75
˚C
600
V class
2
heat resistant indoor PVC wire.
Assume the following usage conditions
:
·
Ambient temperature
:
40
˚C or lower
·
Wiring distance
:
100
m or shorter
·
Rated current value