16 UL Standards
116 YASKAWA TOEPC71061723A YASKAWA AC Drive CR700 Quick Start Guide
• 400 V Class
Use the fuses specified in this document to prepare the drive for use on a circuit that supplies not more than
100,000 RMS and not more than 480 Vac when there is a short circuit in the power supply.
The built-in short circuit protection of the drive does not provide branch circuit protection. The user must provide
branch circuit protection as specified by the National Electric (NEC), the Canadian Electric Code, Part I (CEC),
and local codes.
Three-Phase 200 V Class
Table 16.5 Factory-Recommended Branch Circuit Protection
Drive Model
Maximum Applicable Motor Output
kW (HP)
Input Current Rating
A
Semiconductor Protection Fuse
Rated Current
Manufacturer: EATON/Bussmann
2003 0.55 (0.5) 3.6 FWH-45B
2005 0.75 (1) 4.8 FWH-45B
2008 1.5 (2) 8.9 FWH-45B
2011 2.2 (3) 12.7 FWH-50B
2014 3 (4) 17 FWH-80B
2018 4.0 (5) 20.7 FWH-80B
2025 5.5 (7.5) 30 FWH-125B
2033 7.5 (10) 40.3 FWH-150B
2047 11 (15) 58.2 FWH-200B
2060 15 (20) 78.4 FWH-225A
2075 18.5 (25) 96
FWH-225A
FWH-250A
*1
2088 22 (30) 82
FWH-225A
FWH-250A
*1
2115 30 (40) 111
FWH-275A
FWH-300A
*1
2145 37 (50) 136
FWH-275A
FWH-350A
*1
2180 45 (60) 164
FWH-325A
FWH-450A
*1
2215 55 (75) 200 FWH-600A
2283 75 (100) 271 FWH-800A
2346 90 (125) 324 FWH-1000A
2415 110 (150) 394 FWH-1400A
*1 Yaskawa recommends a fuse with a large rated current for applications with repeated loads.
Three-Phase 400 V Class
Table 16.6 Factory-Recommended Branch Circuit Protection
Drive Model
Maximum Applicable Motor Output
kW (HP)
Input Current Rating
A
Semiconductor Protection Fuse
Rated Current
Manufacturer: EATON/Bussmann
4002 0.55 (0.75) 1.9 FWH-50B
4003 1.1 (1) 3.5 FWH-50B
4005 1.5 (2) 4.7 FWH-50B
4006 2.2 (3) 6.7 FWH-60B
4007 3 (4) 8.9 FWH-60B
4009 4.0 (5) 11.7 FWH-60B
4015 5.5 (7.5) 15.8 FWH-80B
4018 7.5 (10) 21.2 FWH-90B
4024 11 (15) 30.6 FWH-150B
4031 15 (20) 41.3 FWH-200B
4039 18.5 (25) 50.5 FWH-200B