9
For YASKAWAs inverter motor with PG, PG is installed at the opposite drive
end. Then, phase A lags phase B by a phase angle of 90_ at motor forward run.
(Motor runs CCW as viewed from PG.) Therefore, when using this motor or
similar motors, connect phases A and B to the option card after replacing phase
output. The pulse monitor on this option shows phase A leading phase B by a
phase angle of 90_.
Make sure the followings when wiring.
S To prevent noise, use shielded wire and separate from heavy current circuits
(200VAC or greater) or relay drive circuits. (Wire length to the PG connec-
tor must be 50m or shorter.)
S Connect both ends of the unused wire of the shielded wire to the 0V termi-
nal.
S Connect the grounding lead wire (E) to pin 12 of the control board of the
inverter.
S Applicable wire sizes for terminal block TA1 and TA2 are shown below.
[Terminal: MKDS1 series manufactured by Phoenix Contact GmbH &
Co.]
[mm
2
] AWG I [A] VAC [V]
Thin twisted wire
1 16 12 125
Solid wire
1.5 16 12 125
UL
2216 10 300
CSA
2816 10 300
CSA
2816 10 150
Terminal block TA1,TA2 side
Connecting wire end
5.5 mm
Notes on selecting cables
Too thick a cable applies pressure to the option card and may lead to failure.
Too thin a cable may lead to imperfect contact or a break in the wire.
NOTE