EasyManua.ls Logo

YASKAWA VARISPEED-616G5 - Page 164

YASKAWA VARISPEED-616G5
355 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Advanced Operation
7.1.5 Starting Torque Compensation Function (for SPEC:F)
7-10
D
Set the constant for starting torque compensation (C4-05) to a large value if a shock is generated during
startup.
Alternatively, use DC injection braking (b2-03) at startup or the DC braking command for multifunc-
tion contact input (setting: 60), and start motor magnetic flux before startup.
(Magnetic flux using DC injection braking at start (b2-03) can be started earlier. Refer to Magnetic flux
compensation under 7.5.1 Application Constants: b)
7

Table of Contents

Other manuals for YASKAWA VARISPEED-616G5

Related product manuals