7.5 Common Functions
7-61
J
Analog Monitor Card: F4-01 to F4-04
D
When using an AO-08 or AO-12 Analog Monitor Card, set the monitor items and gain with the follow-
ing constants.
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
F4-01
Channel 1 monitor
selection
×
1to38 2
B B B B
F4-02
Channel 1 gain
f
0.00 to 2.50
Mul-
tiple
1.00
B B B B
F4-03
Channel 2 monitor
selection
×
1to38 3
B B B B
F4-04
Channel 2 gain
f
0.00 to 2.50
Mul-
tiple
0.50
B B B B
F4-05
Channel 1 output
bias
f
10.0 to
+10.0
% 0.0
B B B B
F4-06
Channel 2 output
bias
f
10.0 to
+10.0
% 0.0
B B B B
F4-02
(F4-04)
AO
F4-05
(F4-06)
Output bias
Output gain
+
+
Fig 7.33 Analog Output Block Diagram
D
For the output monitor selections (F4-01, F4-03), set the numbers for the right side of the “U1”
constants in the Table 4.3. The setting range is 1 to 38, but the following numbers cannot be set: 4, 10,
11, 12, 13, 14, 25, and 28 to 35.
D
When the AO-12 is used, outputs of 0 to ±10 V are possible. For that, set constant H4-07 (multi-func-
tion analog output signal level selection) to “1” (0 to ±10 V outputs). There are some monitor items.
However, that can only use outputs of 0 to +10 V even if constant H4-07 is set to “1.”
D
When the AO-08 is used, only outputs of 0 to +10 V are possible regardless of the constant H4-07 set-
ting.
J
DO-02 Digital Output Card Settings: F5-01, F5-02
D
Set the output selections in the following constants when using a DO-02 Digital Output Card.
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
F5-01
Channel 1 output
selection
×
00 to 37 0
B B B B
F5-02
Channel 2 output
selection
×
00 to 37 1
B B B B
D
Set the values from Table 7.10.