EasyManua.ls Logo

YASKAWA VS-686SS5 - Page 81

YASKAWA VS-686SS5
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
82
For Models CIMR-SSA4220 to -SSA4300 (400V Class 220 to 300 kW)
16 Multi-function Analog Input
0 to 10V (20k)
Voltage
Selection
460/440/415/
400/380V
400
( 2 400)
B
BB
Braking
Resistor
Unit :
Braking
Resistor
Unit
U
V
W
MCCB
3-Phase
Power Supply
380 to 460 V
50/60 Hz
R
MC
S
T
400/200V
R
S
T
M
r
Cooling
Fan
Motor
M
Thermal Overload
Protector
1
2
P
1
2
34
Thermoswitch
5
6
Level
Detection
MASTER
+15
Braking Unit 3
Braking Unit 2
1
2
34
Thermoswitch
5
6
MASTER
SLAVE
P
P
Thermal Overload
Protector
1
2
Braking
Resistor
Unit
P
Thermal Overload
Protector
12
P
MASTER
SLAVE
34
Thermoswitch
5
6
1
2
¨ 1 ©¨ 3
THRX OFF
ON
MC
SA
Overload Relay Trip Contact
of Braking Resistor Unit
12
MC
TRX
TRX
20
18
Fault
Contact
SA
SA
THRX
MC
Braking Unit
3
4
Forward Run/Stop
Reverse Run/Stop
Factory
Setting
External Fault
Fault Reset
Multi-step Speed Setting 1
(Master/Aux Change)
Multi-step Speed
Setting 2
Jog Reference
External Baseblock
3
4
5
6
7
8
Analog
Monitor 1
17 (Aux Speed Ref. at
Factory Setting)
15 Speed Setting Power
Supply +15V 20mA
11
0V
1 Forward Run when
CLOSED
2 Reverse Run when
CLOSED
Multi-function
Contact Input
Sequence Common
Terminal (0V)
12 Shield Sheath
Connection Terminal
13 Master Speed Ref.
0 to 10V (20k)
14 Master Speed Ref.
4 to 20mA (250)
33 Speed Setting Power Supply
-15V 20mA
Ground (10 or less)
(12)
21
22
23
+
AM
+
SM
Multi-function Analog Output
-10 to +10 V 2mA
(Rotation Speed at Factory
Setting)
18
Multi-function Open
Collector Output
48 V 50 mA or less
Multi-function
Output Common
27
Open Collector 2
(Speed Agree Signal
at Factory Setting)
26
Open Collector 1
(Zero Speed Signal at
Factory Setting)
25
Multi-function Contact Output
250 VAC 1 A or less
30 VDC 1A or less
(Signal during Running at Factory
Setting)
10
9
20
19
Fault Contact Output
250 VAC 1 A or less
30 VDC 1 A or less
2k
2k
0 to +10 V
4to20mA
P
0 to +10 V
P
0V
P
Multi-function Analog Output
-10 to +10V 2mA
(Output Current at Factory
Setting)
Analog
Monitor 2
(
1
)
Use sequencer to break
power supply side on
overload relay trip contact
of braking resistor unit.
VS-686SS5
¨
0
¨©©
0
¨
0
¨©©
0
¨
0
¨©©
0
External
Speed
Reference
: When using the braking resistor unit, set constant L3-01 to “0” (overvoltage prevention selection
disabled). If it is not changed, the inverter may not stop within set decel time.
18
20

Table of Contents

Related product manuals