IM 01C21C01-01E
8-15
8. BRAIN TERMINAL BT200 OPERATION
(14) User Memo Fields (M: MEMO)
This feature provides 5 user memo fields, each holding
up to 8 alphanumeric characters. Up to 5 items such as
inspection date, inspector, and other information can be
saved in these fields.
• Example: Save an inspection date of January
30, 1995.
DATA DIAG PRNT ESC
SET
M10:MEMO 1
95.1.30_
ESC
PARAM
M10:MEMO 1
M20:MEMO 2
M30:MEMO 3
Set 95.1.30 in the order of year,
month, and day.
Press the key twice to
enter the setting.
F0835.EPS
8.4 Displaying Data Using the
BT200
8.4.1 Displaying Measured Data
The BT200 can be used to display measured data.
The measured data is updated automatically every 7
seconds. In addition, the display can be updated to the
present data value at any time by pressing the
(DATA) key. For parameters associated with the
display of measured data, see Subsection 8.3.1,
“Parameter Summary.”
• Example: Display output.
DATA DIAG PRNT ESC
PARAM
A10:OUTPUT (%)
A11:ENGR.OUTPUT
A20:AMP TEMP
HOME SET ADJ ESC
MENU
A:DISPLAY
B:SENSOR TYPE
F0836.EPS
Data is updated automatically
at 7-second intervals.
Display “A10: OUTPUT (%).”
PARAM
A10:OUTPUT (%)
XX.X %
A11:ENGR.OUTPUT
YY.Y %
A20:AMP TEMP
ZZ deg C
communi
8.4.2 Display Transmitter Model and
Specifications
The BT200 can be used to display the model and
specifications of the transmitter.
• Example: View transmitter model name.
HOME SET ADJ ESC
MENU
A:DISPLAY
B:SENSOR TYPE
DATA DIAG PRNT ESC
PARAM
B10:MODEL
EJA210A-DM
B11:STYLE NO.
S1.01
B20:LRL
– 98.07 kPa
Press .
F0837.EPS
For the associated
parameters, see Subsection
8.3.1, Parameter Summary.