EasyManua.ls Logo

YOKOGAWA DX1000 - RSLogix Tag Definition

YOKOGAWA DX1000
21 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19
IM 04L41B01-18E
Example of I/O Message Using RSLogix 5000
Connection with DX
First,definethe connection with DXusingRSLinx. Go to Communicationonthe menu
barandselectConfigureDrivers.
Next,selectEthernetDevicesandclickAddNew....
Entera drivername. In this example, DXADV is enteredbut other names can also be
entered.
EntertheIPaddressofDXandclickOK.
DXisdisplayedontheRSWholistofRSLinx.
Configuration of Communication Settings
Open RSLogix 5000 and select a PLC used to communicate with DX. Right-click
EthernetinI/OConfigurationandselectNewModule.
Click + to open the list. Select ETHERNET-MODULE and click OK.An ETHERNET-
MODULEsetupwindowwillopen.
The following shows an example of reading data in measurement channels 001 to 010
and writing the data to communication input data C01 to C20. Data can be accessed
using the INT32 type.
IntheNamefield,enterDXADV(orothercommunicationconnectionname).Sincedata
isaccessedusingINT32,keepCommFormatasData-DINT.InIPAddress,entertheIP
address of DX.
In Connection Parameter, define the input and output. In Input and Output, enter a
respectiveinstanceIDandsize.InConfiguration,enteraninstanceIDof190andasize
of 0.
New Module
Name DXADV
Comm Format Data-DINT
Address/Host Name
IPAddress 10.0.232.126
Connection Parameter
Assembly Instance Size
Input 1
10 10 (32-bit)
Output 13
0 20 (32-bit)
Configuration 190 0 (8-bit)
Tag
InControllerTag,theDXADV:IandDXADV:Otagstobeusedincontrollogichavebeen
made.Click+toexpandthetagandseeallthepointsofasizespecifiedinthemodule
definition.

Related product manuals