EasyManua.ls Logo

YOKOGAWA SMARTDAC+ GP10 - Page 29

YOKOGAWA SMARTDAC+ GP10
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21
IM 04L51B01-18EN
Explicit Message
Datatobeaccessed Tagname SupplementaryInformation
Datatype
INT32
Individual alarm ACK
(alarm ACK Channel level)
dint[12653] 0: Fixed at 0 when reading
1: Alarm level 1 ACK
2: Alarm level 2 ACK
3: Alarm level 3 ACK
4: Alarm level 4 ACK
• Read/Writemessage
Message writing is executed when a message (free message or preset message) is written
in the message body. In the case of a preset message, the written content is ignored.
Datatobeaccessed Tagname SupplementaryInformation
Datatype
INT32
Datatype
STRING
Write a message
(specify the write method)
dint[12700] 0: Fixed at 0 when reading
1: Write a preset message
2: Write a free message
Write a message
(message number)
dint[12701] 0: Fixed at 0 when reading
Preset message: 1 to 100
Free message: 1 to 10
Write a message
(specify the write destination)
dint[12702] 0: All display groups; fixed at
0 when reading
1 or greater: The specified
display group
Write a message
(batch group number)
dint[12703] 0: Fixed at 0 when reading
1 or greater: Batch group
number
Write a message
(body of message)
dint[12704] string[12704] 0: Fixed at 0 when reading
UTF-8 characters (2
characters)
Up to 35 characters (except
the number of valid characters
is 32)
Message writing is executed
when a message is written
here.
Ignored for preset messages
Attach a terminator ‘\0’ at the
end
• Read/Writebatchinformation
Lot number, Batch number, Batch gropu number
The content is reflected when the lot number or batch number is updated.
when multi batch is not in use
Datatobeaccessed Tagname SupplementaryInformation
Datatype
INT32
Datatype
STRING
Lot number dint[12800] Lot number data
Batch number dint[12801] string[12801] UTF-8 characters (2
characters)
Up to 32 characters [attach
the terminator ‘\0’ at the end]
When multi batch is in use
Datatobeaccessed Tagname SupplementaryInformation
Datatype
INT32
Datatype
STRING
Batch group number dint[12850] 1 or greater: Batch group
number
When reading, the batch
group number that performed
writing previously
Default value: 0
Continued on next page

Related product manuals