<Toc> <2. Initial Settings>
2-5
IM 05F01D02-41E
■ Instrument Input Range Codes
Input Type
Instrument Input
Range Code
Instrument
Input Range
Measurement Accuracy
OFF
1
Set the data item PV Input Type "IN" to the OFF option to leave the PV input
type undefined.
2
K
J4
5
T
6
⫾0.1% of instrument range ⫾1 digit for temperatures
equal to or higher than 0°C
⫾0.2% of instrument range ⫾1 digit for temperatures
below 0°C
⫾0.1% of instrument range ⫾1 digit for temperatures
equal to or higher than 0°C
⫾0.2% of instrument range ⫾1 digit for temperatures
below 0°C
B7
⫾0.15% of instrument range ⫾1 digit for temperatures
equal to or higher than 400°C
⫾5% of instrument range ⫾1 digit for temperatures
below 400°C
S8
R9
⫾0.15% of instrument range ⫾1 digit
N10
⫾0.1% of instrument range ⫾1 digit
⫾0.25% of instrument range ⫾1 digit for temperatures
below 0°C
E11
L(DIN) 12
13
U(DIN)
14
W15
⫾0.2% of instrument range ⫾1 digit
Platinel 2 16
⫾0.1% of instrument range ⫾1 digit
PR20-40 17
⫾0.5% of instrument range ⫾1 digit for temperatures
equal to or higher than 800°C
No guarantee of accuracy for temperatures below 800°C
Thermocouple
Unspecified
W97Re3-
W75Re25
18
⫾0.2% of instrument range ⫾1 digit
30
⫾0.1% of instrument range ⫾1 digit (Note 1) (Note 2)
JPt100
31
⫾0.2% of instrument range ⫾1 digit (Note 1)
35
36
⫾0.1% of instrument range ⫾1 digit (Note 1) (Note 2)
RTD
Pt100
37
⫾0.2% of instrument range ⫾1 digit (Note 1)
0.4 to 2 V
40
Standard
signal
1 to 5 V 41
0 to 2 V 50
0 to 10 V 51
0.400 to 2.000 V
1.000 to 5.000 V
0.000 to 2.000 V
0.00 to 10.00 V
-10 to 20 mV
55 -10.00 to 20.00 mV
DC voltage
0 to 100 mV
56 0.0 to 100.0 mV
⫾0.1% of instrument range ⫾1 digit
The read-out range can be scaled between -1999 and
9999.
3
Set the data item PV Input Type "IN" to the OFF option to leave the PV input
type undefined.
-200 to 1370⬚C
-300 to 2500⬚F
-199.9 to 999.9⬚C
0 to 2300⬚F
-199.9 to 500.0⬚C
-199.9 to 999.9⬚F
-199.9 to 999.9⬚C
-300 to 2300⬚F
-199.9 to 400.0⬚C
-300 to 750⬚F
0.0 to 400.0⬚C
-199.9 to 750.0⬚F
0 to 1800⬚C
32 to 3300⬚F
0 to 1700⬚C
32 to 3100⬚F
0 to 1700⬚C
32 to 3100⬚F
-200 to 1300⬚C
-300 to 2400⬚F
-199.9 to 999.9⬚C
-300 to 1800⬚F
-199.9 to 900.0⬚C
-300 to 1300⬚F
-199.9 to 400.0⬚C
-300 to 750⬚F
0.0 to 400.0⬚C
-199.9 to 750.0⬚F
0 to 2300⬚C
32 to 4200⬚F
0 to 1390⬚C
32 to 2500⬚F
0 to 1900⬚C
32 to 3400⬚F
0 to 2000⬚C
32 to 3600⬚F
-199.9 to 500.0⬚C
-199.9 to 999.9⬚F
-150.0 to 150.0⬚C
-199.9 to 300.0⬚F
-199.9 to 850.0⬚C
-300 to 1560⬚F
-199.9 to 500.0⬚C
-199.9 to 999.9⬚F
-150.0 to 150.0⬚C
-199.9 to 300.0⬚F
* Performance in the standard condition (at 23⫾2⬚C, 55⫾10%RH, and 50/60 Hz power frequency.
Note 1: The accuracy is ⫾0.3⬚C of instrument range ⫾1 digit for a temperature range from 0⬚C to 100⬚C.
Note 2: The accuracy is ⫾0.5⬚C of instrument range ⫾1 digit for a temperature range from -100⬚C to 200⬚C.
* To receive a 4-20 mA DC signal, select a standard signal of 1 to 5 V DC and connect it to a 250 ⍀ resistor. This
resistor is optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
1st Edition : May 31,2000-00