Setup Procedure
UTAdvanced Quick Setting (pH Control)
TI 04L01L01-01EN
Foreword
The contents of this document are subject to change without prior notice as a result of improvements in performance or functionality.
Copying or reproduction by any means of all or any part of the contents of this document without permission is strictly prohibited.
Use of this document is at the users risk.
This document is subject to change without notice.
TI 04L01L01-01EN
2011.12.16 1st Edition (YK)
Technical
Information
■ Overview
This is an example of wiring and settings using the UTAdvanced Quick Setting function for "pH Control."
For more details, see the user's manual.
■ Relevant models
Standard models of the UT52A and UT55A (if there are 2 types of pharmaceuticals, select the
heating/cooling model)
■ System
■ Wiring
Sampling can be controlled to interpolate dead time
Current input signal
4–20 mA
Current input signal
4–20 mA
Plant A waste liquid -->
Plant B waste liquid -->
Plant C waste liquid -->
Chemical dosing pump
pH meter
converter
0–14 pH
pH meter
sensor
Effluent
■ Sampling control
■ Nonlinear t
e
Control gain is switched by the Gap Gain Control
function
Current input
4–20 mA
PV
Current
input
Power
supply
-
+
203
Current output
4–20 mA
+
-
UT52A, UT55A Standard Models
pH meter
+
-
Current
output
4–20 mA
PV
Transmission
output