Peel the jacket off for this length
Cable
Core
Figure 5.2.1-2 Cable
l
Cables Used
600 V polyvinyl chloride insulated wires (IV): JIS C 3307/IEC 60227-3
Polyvinyl chloride insulated wires for electrical apparatus (KIV): JIS C 3316/IEC 60227-3
600 V grade heat-resistant polyvinyl chloride insulated wires (HIV): JIS C 3317/IEC
60227-3
Heat-proof vinyl insulated wires VW-1 (UL1015/UL1007)
Control cables (vinyl insulated vinyl sheath cable) (CVV): JIS C 3401
l
Recommended Cable Thickness
Without sleeve : 0.5 mm
2
to 2 mm
2
(AWG20 to 14)
With sleeve : 0.5 mm
2
to 1.5 mm
2
(AWG20 to 16)
l
Wiring to Pressure Clamp Terminals (without Sleeves)
Table 5.2.1-2 Wiring to Pressure Clamp Terminals without Sleeves
Cable thickness (mm
2
)
Peel-off length (mm)
0.5 to 2 (AWG20 to 14) 11
l
W
iring to Pressure Clamp Terminals (with Sleeves)
Table 5.2.1-3 Wiring to Pressure Clamp Terminals with Sleeves
Cable
thickness
(mm
2
)
When using a sleeve with insulating cover
When using a sleeve (without insulating
cover)
Peel-off
length
(mm)
Sleeve dimension (mm)
Weidmul-
ler model
Peel-off
length
(mm)
Sleeve dimension
(mm)
Weidmul-
ler model
L1 L2 d1 d2 L1 d1 d2
0.5 11 16 10 1.0 2.6 H0.5/16 11 10 1.0 2.1 H0.5/10
0.75 11 16 10 1.2 2.8 H0.75/16 11 10 1.2 2.3 H0.75/10
1.0 11 16 10 1.4 3.0 H1/16 11 10 1.4 2.5 H1/10
1.25 to
1.5
11 16 10 1.7 3.5 H1.5/16 11 10 1.7 2.8 H1.5/10