L1
L2
d2
d1
L1
d2
d1
Sleeve with insulating cover
Sleeve (without insulating cover)
IMPORTANT
Use pressure clamp terminal sleeves and tools from the same manufacturer.
Use pressure clamp terminal sleeve tools suitable for the thickness of the wires.
Plug the cables to be connected deep into the pressure clamp terminals and make sure
they are securely installed.
It is recommended to use a driver that conforms to the DIN 5264B standard. The stand-
ard requires a screwdriver with a thickness of 0.6 mm at the tip and a body shaft diameter
of 3.5 mm for the cable connection.
The tightening torque is 0.5 N•m
Fasten the cables securely to cable clamps, etc., so that the cables do not weigh on the
terminals.