280241-YIM-D-0909
Johnson Controls Unitary Products 7
Duct work should be designed and sized according to the 
methods of the Air Conditioning Contractors of America 
(ACCA), as set forth in their Manual D.
A closed return duct system shall be used. This shall not pre-
clude use of economizers or ventilation air intake. Flexible 
joints may be used in the supply and return duct work to min-
imize the transmission of noise.
NOTE: Be sure to note supply and return openings.
Refer to Figures 11 and 12 for information concerning rear 
and bottom supply and return air duct openings.
ROOF CURB
On applications when a roof curb is used, the unit must be 
positioned on the curb so the front of the unit is tight against 
the curb.
FILTERS
Single phase units are shipped without a filter or filter racks. It 
is the responsibility of the installer to secure a filter in the 
return air ductwork or install a Filter/Frame Kit (1FF0110 for 2 
thru 3½ ton units or 1FF0112 for 4 thru 5 ton units).
A filter rack and high velocity filters are standard on three 
phase units.
Filters must always be used and must be kept clean. When 
filters become dirt laden, insufficient air will be delivered by 
the blower, decreasing your units efficiency and increasing 
operating costs and wear-and-tear on the unit and controls.
Filters should be checked monthly; this is especially impor-
tant since this unit is used for both heating and cooling.
CONDENSATE DRAIN
A condensate trap is recommended to be installed in the con-
densate drain. The plumbing must conform to local codes.
Use a sealing compound on male pipe threads. Install the 
condensate drain line (NPTF) to spill into an open drain.
SERVICE ACCESS
Access to all serviceable components is provided by the fol-
lowing removable panels:
• Blower compartment
• Gas control/electrical service access
Refer to Figure 10 for location of these access panels and 
minimum clearances in Table 12.
THERMOSTAT
The room thermostat should be located on an inside wall 
approximately 56" above the floor where it will not be subject 
to drafts, sun exposure or heat from electrical fixtures or 
appliances. Follow manufacturer's instructions enclosed with 
the thermostat for general installation procedure. Color coded 
insulated wires (minimum #18 AWG) should be used to con-
nect thermostat to unit. See Figures 3 thru 5.
POWER AND CONTROL WIRING
Field wiring to the unit must conform to provisions of the cur-
rent N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordi-
nances. The unit must be electrically grounded in accordance 
with local codes or, in their absence, with the N.E.C./C.E.C. 
Voltage tolerances which must be maintained at the com-
pressor terminals during starting and running conditions are 
indicated on the unit Rating Plate and Table 10.
The wiring entering the cabinet must be provided with 
mechanical strain relief.
A fused disconnect switch should be field provided for the 
unit. If any of the wire supplied with the unit must be replaced, 
replacement wire must be of the type shown on the wiring 
diagram.
Electrical line must be sized properly to carry the load. Each 
unit must be wired with a separate branch circuit fed directly 
from the meter panel and properly fused.
Refer to Figure 6 for typical field wiring and to the appropriate 
unit wiring diagram for control circuit and power wiring infor-
mation.
When fastening duct work to the side duct flanges 
on the unit, insert the screws through the duct 
flanges only. Do not insert the screws through the 
casing. Outdoor ductwork must be insulated and 
waterproofed.
Hand tighten only.