EasyManua.ls Logo

York Champion Series - Page 9

York Champion Series
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Unitary Products Group 9
66297-YIM-C-0205
TABLE 13 - HEATING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,200 CFM (B1HH036)
TABLE 12 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,200 CFM (B1HH036)
INDOOR DB
TEMPERATURE,
°F
HEATING SUPERHEAT AT COMPRESSOR SUCTION, °F
-100 102030405060
55 — — 3.3 4.1 5.3 7.0 9.5 13.2
70 ————3.85.58.011.7
80 ——————4.58.2
OUTDOOR
TEMPERATURE,
°F
INDOOR WB TEMPERATURE, °F
55 57 59 61 63 65 67 69 71 73 75
65 — 5.2 7.3 9.4 11.6 13.7 15.8 20.0 24.2 28.4 32.6
70 — — 6.4 8.2 10.0 11.8 13.6 17.9 22.2 26.5 30.8
75 — — 5.5 6.9 8.4 9.8 11.3 15.7 20.2 24.6 29.1
80 — — — 5.7 6.8 7.9 9.1 13.6 18.2 22.7 27.3
85 ————5.26.06.811.516.2 20.8 25.5
90 ———————9.314.2 19.0 23.8
95 ———————7.212.1 17.1 22.0
100 ———————5.99.914.0 18.0
105 ————————7.710.9 14.0
110 ————————5.57.810.1
115 ——————————6.1
TABLE 10 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,000 CFM (B1HH030)
TABLE 11 - HEATING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,000 CFM (B1HH030)
OUTDOOR
TEMPERATURE,
°F
INDOOR WB TEMPERATURE, °F
55 57 59 61 63 65 67 69 71 73 75
65 — 5.8 10.8 15.8 20.8 25.8 30.8 31.7 32.6 33.4 34.3
70 — 5.1 9.3 13.6 17.8 22.1 26.3 28.0 29.6 31.3 32.9
75 — — 7.9 11.4 14.8 18.3 21.8 24.2 26.7 29.1 31.6
80 — — 6.4 9.1 11.9 14.6 17.3 20.5 23.7 27.0 30.2
85 — — — 6.9 8.9 10.8 12.8 16.8 20.8 24.8 28.8
90 ————5.97.18.313.1 17.9 22.6 27.4
95 ———————9.414.9 20.5 26.0
100 ———————7.612.0 16.3 20.7
105 ———————5.99.012.2 15.3
110 ————————6.18.09.9
115 ———————————
INDOOR DB
TEMPERATURE,
°F
HEATING SUPERHEAT AT COMPRESSOR SUCTION, °F
-100 102030405060
55 — 5.8 7.9 9.6 13.4 19.1 26.9 36.6
70 ————5.411.218.9 28.7
80 —————8.115.9 25.6

Other manuals for York Champion Series