24 YORK INTERNATIONAL
MON XX:XX AM – HIGH PRESSURE
The chiller is shut down because condenser pressure
has increased to 265 PSIG, 1827.2 kPa (R-22); 180
PSIG, 1241.4 kPa (R-134a). System will be allowed to
restart when pressure decreases to 205 PSIG, 1413.5
kPa (R-22); 120 PSIG, 8274 kPa (R-134a). Pressure is
sensed by a High Pressure (HP) safety control that is
located on a mounting bracket above the oil-pump
starter located on the condenser. This message is
prompted by the opening of the HP safety control con-
tacts. To restart chiller, press COMPRESSOR switch
to the STOP/RESET position and then to the START
position.
MON XX:XX AM – EVAP TRANS OR PROBE ERROR
The chiller is shut down because the leaving chilled
water temperature minus the evaporator saturation tem-
perature is outside the range of –2.5°F (–19.2°C) to
+25°F (–3.9°C) continuously for 10 minutes. To restart
the chiller, press COMPRESSOR switch to STOP/RE-
SET switch to STOP/RESET position and then to START
position. On Brine applications (program jumper JP3
removed), this check is not performed when the evapo-
rator transducer is reading a pressure below its “out-
of-range” threshold.
MON XX:XX AM – MOTOR CONTROLLER – EXT. RESET
The chiller is shut down because a current module
(CM-2 Electro-Mechanical starter application), or the
YORK Solid State Starter initiated a shutdown. To re-
start system, reset the external device that caused the
shutdown. The chiller will then automatically restart.
NOTE: The following motor controller shutdowns do
not require an external reset to restart chiller.
Solid State Starter 110°F (43.4°C) start inhibit. Any-
time the chiller has been shut down for any reason,
this message will be displayed until the SCR heatsink
temperatures decrease to below 110°F (43.4°C).
MON XX:XX AM – POWER FAULT – AUTOSTART
The chiller is shut down because of a Solid State Starter
or current module (CM-2 Electro-Mechanical starter
application) “Power Fault” shutdown. The chiller will
automatically restart. This function is sensed by the
motor controller input to the digital input board. A power-
fault shutdown is initiated by the motor controller con-
tacts (CM-1) opening and reclosing in one second. If
Solid State Starter application, the shutdown could have
been caused by any of the following reasons. The ap-
propriate light on the Solid State Starter Logic Board
will be illuminated.
Phase rotation/loss
Trigger Board out of lock (OOL)
Power Fault
Half Phase
MON XX:XX AM – HIGH DISCHARGE TEMP
The chiller is shut down because the discharge tem-
perature has increased to 220°F (104.5°C). The sys-
tem will be allowed to restart when the temperature
has decreased to 219°F (104.0°C). Temperature is
sensed by a thermistor RT2. To restart the chiller, press
COMPRESSOR switch to STOP/RESET position and
then to the START position.
MON XX:XX AM – HIGH OIL TEMP
The chiller is shut down because the oil temperature
has increased to 180°F (82.3°C). The system will be
allowed to restart when the temperature decreases to
179°F (81.7°C). The temperature is sensed by ther-
mistor RT3. To restart the chiller, press COMPRES-
SOR switch to STOP/RESET position and then to the
START position.
MON XX:XX AM – OIL PRESSURE TRANSDUCER
The chiller is shut down because the oil pressure has
increased to 125 PSID, 861.8 kPa (during the first 7
minutes of compressor operation) 60 PSID, 413.7 kPa
(after the first 7 minutes of compressor operation). The
chiller will be allowed to restart when the oil pressure
decreases to 59 PSID, 406.8 kPa. To restart the chiller,
press COMPRESSOR switch to STOP/RESET posi-
tion and then to the START position.
MON XX:XX AM – FAULTY COND PRESSURE XDCR
The chiller is shut down because the condenser trans-
ducer is indicating a pressure of less than 24.2 PSIG,
166.9 kPa (R-22), 6.8 PSIG, 46.9 kPa (R-134a); or a
pressure greater than 300 PSIG, 2069 kPa (R-22 or
R-134a). This is generally indicative of a defective con-
denser transducer or the transducer has been discon-
nected. After the problem has been corrected, the
chiller can be restarted. To restart, press COMPRES-
SOR switch to STOP/RESET position and then to
START position.
MON XX:XX AM – FAULTY OIL PRESSURE XDCR
The chiller is shut down because either the high side
or low side oil pressure transducer was out-of-range
(displaying x’s) while chiller was running. To restart
chiller, press COMPRESSOR switch to STOP/RESET
position and then to START position.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York CodePak YK L1 L1 G4 and is the answer not in the manual?

York CodePak YK L1 L1 G4 Specifications

General IconGeneral
BrandYork
ModelCodePak YK L1 L1 G4
CategoryChiller
LanguageEnglish

Related product manuals