Johnson Controls Unitary Products 11
923180-UTG-A-1112
OPERATION DATA
Notes:
Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent. (Thermistor thermometer).
Connecting piping condition: 25 ft.
P: pressure of air pipe connected to the indoor and outdoor units (gas valve side),
T1: Inlet and outlet temperature for evaporator,
T2: Inlet and outlet temperature for condenser.
Capacity ratio(%)
Capacity ratio(%)
Outdoor Temp (
°F)
Outdoor Temp (
°F)
90 95 100 108 118
60
70
80
90
100
110
120
50
40 40
50
120
110
100
90
80
70
60
504532185
30K Unit
Cooling
Heating
Outdoor Temp (
°F)
Outdoor Temp (
°F)
36K Unit
Cooling
Heating
Capacity ratio(%)
Capacity ratio(%)
90 95 100 108 118
60
70
80
90
100
110
120
50
0404
50
120
110
100
90
80
70
60
504532185
Temperature Condition (°F)
Model name
Standard
Pressure
Heat Exchanger
Pipe Temperature
Indoor Fan
Mode
Outdoor Fan
Mode
Compressor
Frequency (Hz)
Indoor Outdoor P (MPa) T1 (°F) T2 (°F)
COOLING
80/67 95/75
09K 1.05 59 98.6
Turbo High
46
12K 0.93 57.2 98.6 70
18K 0.9 to 1.1 53.6 to 57.2 109.4 to 105.8 77
24K 0.8 to 1.0 50 to 53.6 181.4 to 113 72
HEATING
70/60 47/43
09K 2.62 107.6 41
Turbo High
56
12K 2.77 115 41 72
18K 2.2 to 2.4 100.4 to 98.6 35.6 to 39.2 80
24K 2.5 to 2.7 111.2 to 107.6 32 to 37.4 80