FORM 100.50-EG3 (802)
19
YORK INTERNATIONAL
TABLE 3 – COOLING PERFORMANCE DATA* – 55 TON MODEL (CONT’D)
46.1°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
40.5°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 177 139 175 120 174 106 173 94 172 80 – –
20388 19 166 159 164 144 162 130 161 116 161 104 161 91
17 166 166 160 162 152 151 149 137 147 127 146 113
22 182 150 181 130 180 115 180 105 178 84 – –
27184 19 175 174 169 157 168 141 167 125 165 111 165 96
17 177 177 170 172 162 164 156 153 154 137 153 121
22 193 166 193 144 193 127 191 128 190 90 – –
32706 19 191 200 181 176 180 159 179 140 175 121 177 104
17 195 195 186 188 179 184 167 174 165 153 164 135
22 195 168 194 146 194 128 193 131 192 91 – –
33980 19 194 202 183 179 181 161 181 142 177 123 178 105
17 197 197 188 190 182 187 169 176 167 156 166 137
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 177 139 175 119 174 106 173 94 172 80 – –
20388 19 166 158 164 144 161 130 161 115 161 104 160 91
17 166 166 160 162 152 151 149 137 147 126 146 113
22 181 150 179 129 178 113 177 98 176 83 – –
27184 19 173 173 166 154 165 140 165 124 164 110 164 95
17 175 175 166 168 160 162 155 152 152 136 151 121
22 185 165 185 141 183 122 184 105 181 87 – –
32706 19 184 192 170 169 171 154 171 136 169 118 168 100
17 187 187 175 176 172 177 164 172 158 150 157 131
22 186 167 185 143 184 123 185 106 182 87 – –
33980 19 185 193 171 171 172 156 172 137 170 119 169 101
17 189 189 176 178 173 178 165 173 159 151 158 133