TABLE 4 – COOLING PERFORMANCE DATA* – 60 TON MODEL (CONT’D)
40.5°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
46.1°C AIR ON CONDENSER COIL
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 208 165 206 143 205 126 205 110 204 94 – –
23786 19 200 187 190 171 190 154 190 137 189 122 188 106
17 197 197 189 191 179 179 177 163 175 150 175 133
22 213 182 212 158 211 139 210 119 209 99 – –
30582 19 210 208 198 188 197 172 197 152 195 133 194 114
17 211 211 202 205 193 197 185 183 180 166 181 147
22 217 195 217 168 216 148 214 125 213 103 – –
35679 19 218 227 204 209 203 185 201 163 199 141 198 119
17 222 222 212 214 204 209 190 197 183 178 185 157
22 218 198 218 171 217 150 215 127 214 104 – –
38228 19 220 229 206 217 204 189 202 166 200 144 199 121
17 224 224 214 217 206 212 192 200 184 181 186 159
CAPACITY (kW) AT ENTERING DRY BULB (°C)
ENTERING
32 30 28 27 25 23
m3/hr
WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
22 199 160 197 138 195 121 194 106 192 91 ––
23786 19 187 187 182 169 182 150 181 134 179 118 178 103
17 190 190 181 183 172 174 167 160 165 147 165 131
22 203 177 203 154 202 134 200 115 199 96 ––
30582 19 200 206 190 187 188 168 188 149 186 130 185 110
17 204 204 192 194 186 190 179 182 173 162 173 144
22 206 190 207 166 206 143 205 121 204 100 ––
35679 19 210 219 195 200 193 180 193 159 191 138 190 115
17 214 214 200 202 197 202 188 196 178 173 178 154
22 207 193 208 169 208 145 206 123 205 100 ––
38228 19 213 222 197 204 194 184 194 162 192 140 191 117
17 216 216 202 204 199 205 190 199 179 176 180 156