4-WAY CASSETTE
TC-17005-rev.1
2-3
Indoor Unit Type
Model (H,Y,C)IC4030B21S (H,Y,C)IC4036B21S (H,Y,C)IC4048B21S
Indoor Unit Power Supply
Nominal Cooling Capacity
1
Btu/h
(kW)
Nominal Heating Capacity
1
Btu/h
(kW)
dB
Outer Dimensions
Height in. (mm) 11-3/4 (298) 11-3/4 (298) 11-3/4 (298) 11-3/4 (298)
Width in. (mm) 33-1/16 (840) 33-1/16 (840) 33-1/16 (840) 33-1/16 (840)
Depth in. (mm) 33-1/16 (840) 33-1/16 (840) 33-1/16 (840) 33-1/16 (840)
Net Weight lbs. (kg) 57 (26) 57 (26) 57 (26) 57 (26)
Refrigerant
Indoor Fan
Airflow Rate cfm
(Hi2-Hi-Me-Lo)
(m
3
/min.)
External Pressure
in.W.G
(Pa)
Motor Nominal Output W
Connections
Refrigerant Piping
Liquid Line in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
Gas Line in. (mm) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)
Condensate Drain
OD in. (mm) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32)
ID in. (mm) 1 (25) 1 (25) 1 (25) 1 (25)
57 127 127
Flare-Nut Connection (with Flare Nuts)
VP25 VP25 VP25
127
VP25
0.0 0.0 0.0
(0) (0) (0)
0.0
(0)
R410A
953-812-635-494 1306-1094-847-706 1306-1236-989-777
(27-23-18-14) (37-31-24-20) (37-35-28-22)
1306-1165-918-741
(37-33-26-21)
(7.9) (10.0) (15.8)
Sound Pressure Level
2
(Overall A Scale)
(Hi2-Hi-Me-Lo)
42-36-32-28 48-43-39-33 48-46-41-37
(11.7)
48-45-40-35
(7.0) (8.8) (14.1)
27,000 34,000 54,000
(10.5)
40,000
4-Way Cassette
(H,Y,C)IC4024B21S
AC 1Phase, 208/230V, 60Hz
24,000 30,000 48,00036,000
Color
Outer Dimensions
Height in. (mm) 1-9/16 (40) 1-9/16 (40)
Width in. (mm) 37-3/8 (950) 37-3/8 (950)
Depth in. (mm) 37-3/8 (950) 37-3/8 (950)
Net Weight lbs. (kg) 14 (6.5) 14 (6.5)
Adaptable Panel Model
P-AP160NA2
(without Motion and Radiation Sensors)
P-AP160NAE1
(with Motion and Radiation Sensors)
Neutral White
1. Nominal capacity is based on combinations within the VRF system and the following conditions:
Cooling Operation Conditions
Indoor Air Inlet Temperature: 80°F DB (26.7°C DB)
67°F WB (19.4°C WB)
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 70°F DB (21.1°C DB)
Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB)
43°F WB (6.1°C WB)
Piping Length: 24 ft. 7-3/16 in. (7.5m)
Piping Lift: 0 ft. (0m)
2. Sound pressure level is based on following conditions.
4.9 ft. (1.5m) beneath the unit.
The above data was measured in an anechoic chamber so that reected sound should be taken into consideration in the eld.