YORK INTERNATIONAL 11
FORM 155.16-O3
UNIT OPERATION
LOCAL OR REMOTE MODE
STEAM OR HOT WATER UNITS
BEGIN
LOCAL
OR REMOTE
START
1
2
LVG
WATER TEMP <
SETPOINT
CYCLING SHUTDOWN-
DISPLAY “DAY-TIME-LVG
WATER TEMP < SETPOINT”
AS STATUS
NO
YES
YES
NO
9
PAGE 43
CYCLING SHUTDOWN-
DISPLAY “DAY-TIME-
STEAM/HOT WATER
VALVE LOADED ABOVE
10%” AS STATUS
STEAM/
HOT WATER
VALVE POS.
> 10%
YES
NO
10
PAGE 43
CLOSE CHILLED WATER
PUMP CONTACTS
TB4-44/45
DISPLAY “COOLING
START SEQUENCE
INITIATED”