EasyManua.ls Logo

York PREDATOR DM120 - Capacity Ratings Imperial; Capacity Ratings Metric

York PREDATOR DM120
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
036-21044-003-A-0304
Unitary Products 13
TABLE 2: CAPACITY RATINGS IMPERIAL
Model
Cooling Capacity
Sound
Rating
(dB)
Nominal
Electric
Heat
Capacity
(kW)
1
Gas Heat Capacity
(80 / 67-95°F)
Input
(MBH)
Output
(MBH)
Temp
Rise (°F)
Gas Line
Size
(in. OD)
Cooling Cap. (MBH) Options MBH EER
090
DM 89 9.00 87
7, 14,
18, 27
- - - -
10 - - - -
120 96 15-45 3/4
15 - - - -
180 144 30-60 3/4
120
DM 116 9.0 85
14, 18,
27, 41
- - - -
15 - - - - 180 144 20-50 3/4
150
DM 138 9.0 84
14, 18,
27, 41
- - - -
15 - - - - 180 144 10-40 3/4
1. Electric heaters rated at 415V. See tables 10 through 12 for kW ratings at 380V.
TABLE 3: CAPACITY RATINGS METRIC
Model
Cooling Capacity
Sound
Rating
(dB)
Nominal
Electric
Heat
Capacity
(kW)
1
Gas Heat Capacity
Input
(kW)
Output
(kW)
Temp
Rise
(°C)
Gas Line
Size
(mm. OD)
(27/19-35°C)
Cooling Cap.
(kW)
Options kW
CoP
2
090
(26.4)
DM 26.1 2.64 87
7, 14,
18, 27
- - -
10 - - - -
35.1 28.1 8.3-25 19.05
15 - - - -
52.7 42.2 17-33 19.05
120
(35.1)
DM 34.0 2.64 85
14, 18,
27, 41
- - - -
15 - - - - 52.7 42.2 11-28 19.05
150
(43.9)
DM 40.4 2.64 84
14, 18,
27, 41
- - - -
15 - - - - 52.7 42.2 5.6-22 19.05
1. Electric heaters rated at 415V. See tables 10 through 12 for kW ratings at 380V
2. CoP = Co-efficient of Performance (CoP = Cooling Capacity (kW) / Power Input (kW))