246721-YTG-C-0606
16 Unitary Products Group
TABLE 3: DR CAPACITY RATINGS
Size Model
Cooling Capacity
ARI Ratings
1
CFM
Sound
Rating
(dB)
2
Nominal
Electric
Heat
Capacity
3
(kW)
Gas Heat Capacity
Gas
Line
Size
(in. OD)
MBH EER IPLV
Input
(MBH)
Output
(MBH)
Seasonal
Efficiency
(%)
Temp.
Rise
(°F)
090
Cooling
Only
90 11.2 11.65 3000 84
--- - --
Electric
Heat
9, 18, 24,
36
-- - - -
Gas Heat - 120 96 80 15-45 3/4
Gas Heat - 180 144 80 30-60 3/4
120
Cooling
Only
116 11.2 11.40 3480 90
--- - --
Electric
Heat
18, 24, 36,
54
-- - - -
Gas Heat - 180 144 80 20-50 3/4
Gas Heat - 240 192 80 35-65 3/4
150
Cooling
Only
148 11.1 11.7 3750 86
--- - --
Electric
Heat
18, 24, 36,
54
-- - - -
Gas Heat - 180 144 80 10-40 3/4
Gas Heat - 240 192 80 25-55 3/4
1.
Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb.
2.
Rated in accordance with ARI 270 standard.
3.
See Table 15.
TABLE 4: UNIT VOLTAGE LIMITATIONS
POWER RATING MIN. MAX.
208/230-3-60
187 252
460-3-60
432 504
575-3-60
540 630