TABLE 8: COOLING CAPACITY DR120 UNIT (ALTERNATE REHEAT MODE)
86 83 80 77 74 71 68 86 83 80 77 74 71 68
72 56 8.891----- 48 9.11891----
67 50 8.421134---- 43 8.7178-----
62 43 8.03224156--- 38 8.3168-----
57 44 7.8372820112-- 37 8.1167-----
72 56 8.88------ 49 9.110------
67 50 8.427177---- 44 8.723133----
62 43 8.0 38 33 24 14 4 - - 39 8.3 28 24 16 6 - - -
57 44 7.8 40 36 32 22 12 1 - 38 8.1 28 23 19 9 - - -
72 56 8.86------ 51 9.13------
67 51 8.4332110---- 45 8.730186----
62 43 8.0 43 43 34 22 10 - - 40 8.3 40 40 33 21 9 - -
57 44 7.8 44 44 44 32 21 9 - 39 8.1 39 39 39 28 16 - -
72 58 8.81------ 52 9.2-------
67 52 8.44127141--- 47 8.7372411----
62 45 8.0 45 45 40 27 14 - - 41 8.3 41 41 38 24 11 - -
57 45 7.8 45 45 45 32 19 6 - 41 8.2 41 41 41 27 14 1 -
72 60 8.8-------54 9.2-------
67 54 8.44833184--- 48 8.8453015----
62 46 8.0 46 46 46 31 17 2 - 43 8.4 43 43 43 28 13 - -
57 47 7.9 47 47 47 32 17 2 - 42 8.2 42 42 42 27 12 - -
72 41 9.5-------33 9.9-------
67 36 9.0124----- 29 9.48------
62 31 8.6 20 16 12 3 - - - 24 9.0 24 24 24 16 7 - -
57 31 8.5 21 16 12 3 - - - 25 8.9 25 25 25 17 8 - -
72 43 9.5-------36 9.9-------
67 38 9.0199----- 31 9.4155-----
62 33 8.6 27 25 20 10 - - - 26 9.0 26 26 24 14 4 - -
57 33 8.5 27 25 23 13 3 - - 27 8.9 27 27 27 17 7 - -
72 45 9.5-------39 9.9-------
67 39 9.02614----- 33 9.32211-----
62 34 8.6 34 34 29 17 5 - - 28 8.9 28 28 24 13 1 - -
57 34 8.5 34 34 34 23 11 - - 29 8.9 29 29 29 17 6 - -
72 46 9.54------ 40 9.917115----
67 40 9.033206---- 34 9.429162----
62 35 8.6-------29 9.0-------
57 35 8.5-------30 8.9-------
72 47 9.6 11 3 -4 -19 -34 - - 41 9.9 41 41 41 26 11 - -
67 42 9.1402510-5-19--35 9.435205----
62 36 8.7-35-42-50-65-80--29 9.0-------
57 36 8.6-49-56-64-79-94--31 8.9-------
72 26 10.3 -------
67 21 9.73------
62 17 9.3 17 17 17 17 17 11 2
1 -
57 19 9.3 19 19 19 19 19 12 4
72 29 10.2 -------
67 24 9.7111-----
62 19 9.3 19 19 19 18 8 - -
2 -
57 22 9.3 22 22 22 21 11 1 -
72 33 10.2 -------
67 27 9.7197-----
62 22 9.3 22 22 20 9 - - -
-
57 24 9.2 24 24 24 12 1 - -
72 33 10.2 29 27 25 12 - - -
67 28 9.72411-----
62 22 9.3-------
57 25 9.3-------
72 34 10.3 34 34 34 34 34 - -
67 28 9.728151----
62 23 9.3 -190 ------
57 25 9.3-------
4000
4500
5000
3000
3500
4000
Sensible Capacity (MBH)
5000
Temperature of Air on Condenser Coil 125°F
4500
5000
3000
3500
Return Dry Bulb (°F) Return Dry Bulb (°F)
Temperature of Air on Condenser Coil 105°F Temperature of Air on Condenser Coil 115°F
3000
3500
4000
4500
Air On Evap.
Coil
Temperature of Air on Condenser Coil 85°F Temperature of Air on Condenser Coil 95°F
CFM
WB
(°F)
Total
Cap.
1
(MBH)
Tot.
Input
2
(kW)
Sensible Capacity (MBH) Total
Cap.
1
(MBH)
Tot.
Input
2
(kW)
These capacities are gross ratings. For net capacity,
deduct air blower motor, MBh = 3.415 x kW. Refer to the
appropriate Blower Performance Table for the kW of the
supply air blower motor.
These ratings include the condenser fan motors (total 1
kW) and the compressor motors but not the supply air
blower motor.
-No sensible cooling capacity.