246721-YTG-C-0606
18 Unitary Products Group
TABLE 6: COOLING CAPACITY DR090 UNIT (ALTERNATE REHEAT MODE)
86 83 80 77 74 71 68 86 83 80 77 74 71 68
72
44 6.6103----- 39 6.9104-----
67 39 6.317114---- 34 6.61482----
62 35 6.02418115--- 29 6.219126----
57 37 5.7 28 21 15 8 2 - - 33 5.9 20 14 8 1 - - -
72 45 6.692----- 40 6.98------
67 41 6.323158---- 35 6.620125----
62 36 6.1 31 28 21 13 5 - - 30 6.3 25 22 17 9 2 - -
57 39 5.7 34 31 27 20 12 4 - 35 6.0 28 25 21 14 6 - -
72 47 6.69------ 41 6.95------
67 42 6.32920112--- 37 6.725168----
62 37 6.1 37 37 30 21 12 4 - 31 6.3 31 31 27 19 10 1 -
57 40 5.7 40 40 39 31 22 13 4 36 6.0 36 36 35 27 18 9 -
72 48 6.710------ 42 7.04------
67 43 6.33424144--- 37 6.7302010----
62 38 6.1 38 38 35 25 15 5 - 32 6.4 32 32 30 20 10 - -
57 41 5.7 41 41 41 31 21 11 1 37 6.0 37 37 36 26 16 6 -
72 50 6.710------ 43 7.03------
67 44 6.4 38 27 16 5 - - - 38 6.7 35 23 12 1 - - -
62 40 6.1 40 40 40 28 17 6 - 33 6.4 33 33 33 22 10 - -
57 42 5.7 42 42 42 31 20 9 - 37 6.0 37 37 37 26 15 4 -
72 7.2 20 17 13 7 - - - 29 7.5 29 29 29 22 16 10 3
67 29
34
6.8126----- 25 7.1103-----
62 25 6.5------- 21 6.8-------
57 29 6.2------- 25 6.5-------
72 35 7.2115----- 30 7.514105----
67 30 6.917102---- 26 7.1157-----
62 26 6.513105---- 22 6.82------
57 30 6.213107---- 26 6.5-------
72 36 7.22------ 31 7.5-------
67 31 6.922145---- 26 7.120112----
62 27 6.6 27 27 24 15 6 - - 23 6.8 23 23 20 11 2 - -
57 31 6.3 31 31 31 22 14 5 - 27 6.6 27 27 27 18 9 1 -
72 36 7.3------- 30 7.6-------
67 32 6.926177---- 26 7.222133----
62 27 6.6 27 27 25 15 5 - - 22 6.9 22 22 21 11 1 - -
57 31 6.3 31 31 31 21 11 1 - 26 6.6 26 26 26 16 6 - -
72 37 7.3------- 30 7.6-------
67 32 7.030198---- 25 7.325154----
62 27 6.7 27 27 27 16 5 - - 22 6.9 22 22 22 10 - - -
57 32 6.4 32 32 32 20 9 - - 26 6.7 26 26 26 15 3 - -
72 25 7.7 25 25 25 25 25 25 19
67 20 7.371-----
62 17 7.0------- * -
57 21 6.8-------
72 25 7.8 18 15 12 4 - - -
67 21 7.4124-----
62 18 7.1------- † -
57 22 6.8-------
72 26 7.8-------
67 21 7.4178-----
62 18 7.1 18 18 16 7 - - - -
57
22 6.8 22 22 22 14 5 - -
72 24 7.9-------
67 20 7.51910-----
62 17 7.2 17 17 16 6 - - -
57 21 6.9 21 21 21 11 1 - -
72 23 7.9-------
67 19 7.51911-----
62 16 7.2 16 16 16 5 - - -
57 20 7.0 20 20 20 9 - - -
These capacities are gross ratings. For net capacity,
deduct air blower motor, MBh = 3.415 x kW. Refer to the
appropriate Blower Performance Table for the kW of the
supply air blower motor.
These ratings include the condenser fan motors (total 1
kW) and the compressor motors but not the supply air
blower motor.
No sensible cooling capacity.
3000
Sensible Capacity (MBH)
Tot.
Input
(kW)
Return Dry Bulb (°F) Return Dry Bulb (°F)
Temperature of Air on Condenser Coil 105°F
2250
2625
3000
3750
Temperature of Air on Condenser Coil 125°F
3375
3750
2250
2625
3375
Temperature of Air on Condenser Coil 115°F
2250
2625
3000
3375
3750
Air On Evap. Coil Temperature of Air on Condenser Coil 85°F Temperature of Air on Condenser Coil 95°F
CFM WB (°F)
Total
Cap.*
(MBH)
Tot.
Input
(kW)
Sensible Capacity (MBH)
Total
Cap.*
(MBH)