528195-YTG-I-0513
Johnson Controls Unitary Products 15
115°F 125°F
1625
77 86.5 7.8 35.6 29.9 22.2 - - - 80.1 8.7 30.4 26.7 19.0 - - -
72 77.9 7.8 48.0 40.3 32.6 24.9 - - 71.7 8.6 44.8 37.1 29.4 21.7 - -
67 69.4 7.8 60.5 50.7 43.0 35.3 27.6 - 63.3 8.6 58.3 47.5 39.8 32.1 24.4 -
62 63.7 7.8 63.7 62.9 50.7 43.0 35.3 27.6 58.0 8.6 58.0 58.0 45.8 38.1 30.4 22.7
1950
77 88.8 7.8 42.4 33.5 24.6 - - - 81.8 8.7 38.8 30.0 21.1 - - -
72 80.0 7.8 53.8 44.9 36.0 27.1 - - 73.2 8.6 50.4 41.5 32.6 23.8 - -
67 71.2 7.8 65.3 56.4 47.4 38.5 29.6 - 64.6 8.6 61.9 53.0 44.2 35.3 26.5 -
62 65.4 7.8 65.4 64.9 55.9 47.0 38.1 29.2 59.2 8.6 59.2 59.2 50.9 42.0 33.2 24.3
57 67.1 7.7 67.1 65.5 56.5 47.6 38.7 29.8 62.4 8.5 62.4 60.2 51.3 42.5 33.6 24.7
2275
77 91.1 7.8 49.3 37.0 26.9 - - - 83.5 8.6 47.3 33.3 23.2 - - -
72 82.1 7.8 59.7 49.5 39.4 29.2 - - 74.7 8.6 55.9 45.9 35.9 25.9 - -
67 73.1 7.8 70.1 62.0 51.9 41.7 31.6 - 65.9 8.6 65.5 58.6 48.6 38.6 28.6 -
62 67.1 7.8 67.1 66.8 61.2 51.0 40.9 30.7 60.4 8.6 60.4 60.4 56.0 46.0 36.0 26.0
57 68.9 7.7 68.9 68.1 61.9 51.7 41.5 31.4 63.7 8.5 63.7 62.6 56.5 46.4 36.4 26.4
2600
77 93.4 7.8 56.1 40.5 29.2 - - - 85.2 8.6 55.7 36.5 25.4 - - -
72 84.2 7.8 65.5 54.1 42.8 31.4 - - 76.2 8.6 61.5 50.3 39.2 28.0 - -
67 74.9 7.8 74.9 67.7 56.3 45.0 33.6 - 67.3 8.6 67.3 64.1 53.0 41.8 30.7 -
62 68.8 7.8 68.8 68.8 66.5 55.1 43.7 32.3 61.6 8.6 61.6 61.6 61.1 49.9 38.8 27.6
57 70.6 7.7 70.6 70.6 67.2 55.8 44.4 33.0 65.0 8.5 65.0 65.0 61.6 50.4 39.3 28.1
2925
72 84.9 7.8 71.9 59.0 46.1 33.2 - - 76.8 8.6 68.0 55.2 42.4 29.5 - -
67 75.6 7.8 75.6 72.0 60.7 47.8 35.0 - 67.8 8.6 67.8 67.6 57.3 44.4 31.6 -
62 69.4 7.8 69.4 69.4 68.2 55.3 42.4 29.5 62.1 8.6 62.1 62.1 61.8 49.0 36.2 23.3
57 71.2 7.7 71.2 71.2 69.5 56.6 43.7 30.8 65.5 8.5 65.5 65.5 63.8 51.0 38.1 25.3
3250
72 85.6 7.8 78.2 63.8 49.4 35.0 - - 77.4 8.6 74.5 60.0 45.5 31.0 - -
67 76.2 7.8 76.2 76.2 65.1 50.7 36.3 - 68.3 8.6 68.3 68.3 61.5 47.0 32.5 -
62 69.9 7.8 69.9 69.9 69.9 55.5 41.1 26.7 62.6 8.6 62.6 62.6 62.6 48.1 33.6 19.1
57 71.8 7.7 71.8 71.8 71.8 57.4 43.0 28.6 66.0 8.5 66.0 66.0 66.0 51.5 37.0 22.5
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
XP078 (6.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65