528195-YTG-I-0513
Johnson Controls Unitary Products 23
115°F 125°F
3125
77 151.0 14.0 61.6 51.9 38.8 - - - 147.4 15.3 52.9 47.4 34.5 - - -
72 139.6 13.9 87.4 74.3 61.1 48.0 - - 134.0 15.2 82.6 69.7 56.8 43.9 - -
67 128.2 13.7 113.3 96.7 83.5 70.3 57.2 - 120.6 15.0 110.2 92.1 79.2 66.2 53.3 -
62 126.2 13.5 126.2 114.1 97.0 83.8 70.7 57.5 123.6 14.7 123.6 105.5 89.6 76.7 63.8 50.9
3750
77 156.0 14.1 73.1 57.9 42.8 - - - 150.7 15.4 68.1 53.1 38.2 - - -
72 144.2 13.9 97.8 82.6 67.5 52.4 - - 136.9 15.2 92.8 77.9 63.0 48.1 - -
67 132.4 13.8 122.5 107.4 92.2 77.1 62.0 - 123.1 15.1 117.6 102.7 87.8 72.9 57.9 -
62 130.4 13.5 130.4 122.3 107.2 92.1 77.0 61.9 126.4 14.8 126.4 114.3 99.4 84.5 69.6 54.7
57 127.3 13.6 127.3 121.7 106.6 91.5 76.4 61.3 122.8 14.9 122.8 114.5 98.1 83.1 68.2 53.3
4375
77 161.0 14.2 84.5 64.0 46.9 - - - 154.0 15.4 83.2 58.9 42.0 - - -
72 148.8 14.0 108.1 91.0 74.0 56.9 - - 139.8 15.3 103.1 86.1 69.2 52.3 - -
67 136.6 13.9 131.6 118.1 101.0 83.9 66.9 - 125.7 15.2 125.1 113.3 96.4 79.5 62.5 -
62 134.5 13.6 134.5 130.5 117.3 100.3 83.2 66.2 129.2 14.9 129.2 123.1 109.2 92.3 75.3 58.4
57 131.3 13.7 131.3 128.6 116.7 99.7 82.6 65.6 125.5 15.0 125.5 121.3 107.7 90.8 73.9 56.9
5000
77 166.0 14.2 95.9 70.0 51.0 - - - 157.3 15.5 98.3 64.7 45.8 - - -
72 153.4 14.1 118.4 99.4 80.4 61.4 - - 142.8 15.4 113.3 94.3 75.4 56.5 - -
67 140.8 13.9 140.8 128.8 109.8 90.7 71.7 - 128.2 15.3 128.2 124.0 105.0 86.1 67.1 -
62 138.7 13.7 138.7 138.7 127.5 108.5 89.5 70.5 132.0 15.0 132.0 132.0 119.0 100.1 81.1 62.2
57 135.4 13.7 135.4 135.4 126.8 107.8 88.8 69.8 128.2 15.1 128.2 128.2 117.4 98.5 79.5 60.6
5625
72 155.5 14.1 127.4 106.8 86.2 65.6 - - 145.2 15.4 121.4 101.0 80.6 60.2 - -
67 142.7 14.0 142.7 136.7 117.7 97.1 76.5 - 130.4 15.3 130.4 130.3 112.3 91.9 71.4 -
62 140.5 13.7 140.5 140.5 135.0 114.3 93.7 73.1 134.2 15.0 134.2 134.2 127.7 107.3 86.9 66.5
57 137.2 13.7 137.2 137.2 132.9 112.3 91.7 71.1 130.3 15.1 130.3 130.3 124.9 104.5 84.1 63.7
6250
72 157.5 14.1 136.4 114.2 92.0 69.8 - - 147.6 15.4 129.6 107.7 85.8 63.9 - -
67 144.6 14.0 144.6 144.6 125.6 103.4 81.2 - 132.7 15.3 132.7 132.7 119.5 97.6 75.7 -
62 142.4 13.7 142.4 142.4 142.4 120.2 98.0 75.8 136.4 15.0 136.4 136.4 136.4 114.5 92.6 70.7
57 139.0 13.7 139.0 139.0 139.0 116.8 94.6 72.4 132.5 15.1 132.5 132.5 132.5 110.6 88.7 66.8
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
XP150 (12.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65