528195-YTG-I-0513
28 Johnson Controls Unitary Products
XP078-150 Bottom Duct Application
XP078 (6.5 Ton) Bottom Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2" filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x .932.
4. Field Supplied Drive.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
FS
4
Standard 1.5 HP & Drive Hi Static 2 HP & Drive
1800 445 0.63 559 0.66 648 0.69 730 0.72 799 0.75 875 0.89 937 0.99 984 1.05 1038 1.08 1086 1.11
2000 486 0.71 589 0.76 674 0.79 753 0.83 820 0.87 898 1.02 960 1.13 1007 1.18 1061 1.21 1109 1.25
2200 530 0.84 624 0.90 705 0.94 781 0.99 846 1.03 924 1.19 988 1.31 1034 1.35 1088 1.39 1137 1.42
2400 567 0.91 653 0.98 729 1.04 801 1.09 867 1.14 944 1.31 1007 1.41 1055 1.47 1108 1.50 1156 1.54
2600 605 1.02 685 1.10 758 1.16 826 1.21 889 1.27 965 1.45 1028 1.55 1075 1.60 1128 1.63 1178 1.67
2800 645 1.16 719 1.24 788 1.29 854 1.36 915 1.43 988 1.60 1051 1.71 1099 1.75 1151 1.80 1201 1.83
3000 686 1.31 757 1.39 822 1.46 885 1.53 943 1.60 1013 1.77 1076 1.88 1123 1.93 1176 1.97 1225 2.00
3200 729 1.49 797 1.57 858 1.64 917 1.73 972 1.81 1038 1.96 1102 2.07 1149 2.11 1203 2.16 1252 2.19
3400 772 1.70 839 1.77 897 1.84 953 1.93 1005 2.03 1066 2.16 1130 2.27 1177 2.31 1230 2.36
FS
4
XP090 (7.5 Ton) Bottom Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
FS
4
Standard 1.5 HP & Drive Hi Static 3 HP & Drive
2000 644 0.11 698 0.38 755 0.62 814 0.85 874 1.06 933 1.26 990 1.46 1043 1.66 1090 1.87 1131 2.09
2200 666 0.26 720 0.53 777 0.77 836 1.00 896 1.21 956 1.41 1012 1.61 1065 1.81 1113 2.02 1153 2.24
2400 689 0.42 743 0.69 800 0.93 859 1.16 919 1.37 978 1.57 1035 1.77 1088 1.97 1135 2.18 1176 2.40
2600 712 0.60 766 0.87 823 1.11 882 1.34 942 1.55 1002 1.75 1058 1.95 1111 2.15 1159 2.36 1199 2.58
2800 736 0.80 790 1.06 847 1.31 906 1.53 967 1.74 1026 1.94 1082 2.14 1135 2.34 1183 2.55 1223 2.78
3000 761 1.00 815 1.27 872 1.52 931 1.74 991 1.95 1051 2.15 1107 2.35 1160 2.55 1208 2.76 1248 2.98
3200 787 1.22 840 1.49 898 1.74 957 1.96 1017 2.17 1076 2.37 1133 2.57 1186 2.77 1233 2.98 1274 3.20
3400 813 1.46 867 1.73 924 1.97 984 2.19 1044 2.40 1103 2.61 1160 2.80 1212 3.01 1260 3.21 - -
3600 841 1.70 894 1.97 952 2.21 1011 2.44 1071 2.65 1130 2.85 1187 3.05 - -----
3800 869 1.96 923 2.22 980 2.47 1039 2.69 1099 2.90 1158 3.10 1215 3.30 - -----
3 HP & Field Supplied Drive
XP102 (8.5 Ton) Bottom Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP & Field Supplied Drive Standard 2 HP & Drive Hi Static 3 HP & Drive
2200 662 0.53 717 0.68 770 0.83 821 0.96 870 1.09 918 1.22 965 1.35 1010 1.47 1055 1.59 1098 1.71
2400 677 0.63 732 0.78 784 0.93 835 1.06 885 1.19 933 1.32 979 1.44 1025 1.57 1069 1.69 1112 1.81
2600 693 0.75 748 0.90 801 1.04 852 1.18 901 1.31 949 1.44 996 1.56 1041 1.68 1085 1.80 1129 1.92
2800 712 0.88 767 1.03 819 1.17 871 1.31 920 1.44 968 1.57 1014 1.69 1060 1.81 1104 1.94 1148 2.06
3000 733 1.03 788 1.18 841 1.33 892 1.46 941 1.59 989 1.72 1036 1.84 1081 1.97 1125 2.09 1169 2.21
3200 757 1.20 811 1.36 864 1.50 915 1.64 964 1.77 1012 1.89 1059 2.02 1104 2.14 1149 2.26 1192 2.38
3400 782 1.40 837 1.55 890 1.69 941 1.83 990 1.96 1038 2.09 1085 2.21 1130 2.33 1174 2.45 1218 2.58
3600 810 1.61 865 1.76 918 1.91 969 2.04 1018 2.18 1066 2.30 1113 2.43 1158 2.55 1203 2.67 1246 2.79
3800 841 1.85 896 2.00 948 2.14 999 2.28 1049 2.41 1097 2.54 1143 2.66 1189 2.78 1233 2.91 1276 3.03
4000 874 2.11 928 2.26 981 2.40 1032 2.54 1082 2.67 1130 2.80 1176 2.92 1222 3.04 1266 3.16 1309 3.28
4200 909 2.38 963 2.53 1016 2.68 1067 2.81 1117 2.95 1164 3.07 1211 3.20 1256 3.32 1301 3.44 - -