528195-YTG-I-0513
36 Johnson Controls Unitary Products
120
(10)
208 16.0 110.0 24.9 1.5 8.2 5.5 0.0
None - - - 47.2 52.7 60 60
E18 13.5 2 37.5 94.0 99.5 100 100
E24 18.0 2 50.0 109.7 115.2 110 125
E36 25.5 2 70.8 135.7 141.2 150 150
E54 40.6 2 112.7 151.1 158.0 175 175
230 16.0 110.0 24.9 1.5 8.2 5.5 0.0
None - - - 47.2 52.7 60 60
E18 18.0 2 43.3 101.3 106.8 110 110
E24 24.0 2 57.7 119.4 124.9 125 125
E36 34.0 2 81.8 149.4 154.9 150 175
E54 54.0 2 129.9 149.4 154.9 150 175
460 7.8 52.0 12.1 0.8 4.1 2.2 0.0
None - - - 23.3 25.5 30 30
E18 18.0 2 21.7 50.3 52.5 60 60
E24 24.0 2 28.9 59.3 61.5 60 70
E36 34.0 2 40.9 74.4 76.6 80 80
E54 54.0 2 65.0 74.4 76.6 80 80
575 5.7 38.9 8.9 0.6 3.6 1.8 0.0
None - - - 17.6 19.4 20 25
E18 18.0 2 17.3 39.3 41.1 40 45
E24 24.0 2 23.1 46.5 48.3 50 50
E36 34.0 2 32.7 58.5 60.3 60 70
E54 54.0 2 52.0 58.5 60.3 60 70
150
(12.5)
208 22.4 149.0 35.0 1.5 10.9 5.5 0.0
None - - - 67.3 72.8 80 90
E18 13.5 2 37.5 114.1 119.6 125 125
E24 18 2 50.0 129.8 135.3 150 150
E36 25.5 2 70.8 155.8 161.3 175 175
E54 40.6 2 112.7 155.8 161.4 175 175
230 22.4 149.0 35.0 1.5 10.9 5.5 0.0
None - - - 67.3 72.8 80 90
E18 18 2 43.3 121.4 126.9 125 150
E24 24 2 57.7 139.5 145.0 150 150
E36 34 2 81.8 169.5 175.0 175 175
E54 54 2 129.9 169.5 175.0 175 175
460 10.6 75.0 16.5 0.8 5.3 2.2 0.0
None - - - 32.4 34.6 40 45
E18 18 2 21.7 59.4 61.6 60 70
E24 24 2 28.9 68.4 70.6 70 80
E36 34 2 40.9 83.5 85.7 90 90
E54 54 2 65.0 83.5 85.7 90 90
575 7.7 54.0 12.0 0.6 4.1 1.8 0.0
None - - - 23.8 25.6 30 30
E18 18 2 17.3 45.5 47.3 50 50
E24 24 2 23.1 52.7 54.5 60 60
E36 34 2 32.7 64.7 66.5 70 70
E54 54 2 52.0 64.7 66.5 70 70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
XP078-150 Standard Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
MCA
1
w/Pwr
Exh
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
Max Fuse
1
/
Breaker
3
Size w/
Pwr Exh
(Amps)
RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps