528195-YTG-I-0513
Johnson Controls Unitary Products 47
Detail A
XP078-150 Unit Bottom Duct Openings
XP078-150 Unit Physical Dimensions
Unit Model Number
Dimension (in.)
ABCDEF
078 50 3/4 89 30 3/16 24 3/16 17 3/16 6 3/16
090 50 3/4 89 30 3/16 24 3/16 17 3/16 6 3/16
102 50 3/4 89 30 3/16 24 3/16 17 3/16 6 3/16
120 50 3/4 89 30 3/16 24 3/16 17 3/16 6 3/16
150 50 3/4 119 1/2 30 3/16 24 3/16 17 3/16 6 3/16
5-3/8
3/4” FPT
XP078-150 Unit Clearances
Direction Distance (in.) Direction Distance (in.)
Top
1
1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge outlet.
72 Right 12
Front 36 Left 36
Rear 36 Bottom
2
2. Units may be installed on combustible floors made from wood or class A, B or C roof covering materials.