036-21584-002 Rev. A (1205)
4 Unitary Products Group
AIR FLOW DATA
HIGH / LOW SPEED COOLING AND HEAT PUMP CFM
40,000 INPUT - 3 Ton 60,000 INPUT - 3 Ton
JUMPER SETTINGS
CFM CFM
High Low High Low COOL Tap ADJ Tap
1340 995 1330 900 A B
1205 885 1130 800 B B
1255 920 1220 850 A A
1150 835 1040 730 B A
1170 855 1120 770 A C
1025 755 920 650 C B
1045 780 950 660 B C
835 625 740 540 D B
950 705 860 610 C A
785 590 690 540 D A
865 665 790 570 C C
725 605 630 530 D C
80,000 INPUT - 3 Ton 80,000 INPUT - 4 Ton
JUMPER SETTINGS
CFM CFM
High Low High Low COOL Tap ADJ Tap*
1310 890 1660 1110 A B
1100 740 1550 1050 B B
1220 830 1610 1070 A A
1000 670 1440 960 B A
1090 720 1470 990 A C
900 610 1370 920 C B
880 610 1290 850 B C
680 510 1130 790 D B
810 580 1230 850 C A
630 500 1050 720 D A
730 530 1110 760 C C
590 500 950 660 D C
100,000 INPUT - 5 Ton 120,000 INPUT - 5 Ton
JUMPER SETTINGS
CFM CFM
High Low High Low COOL Tap ADJ Tap*
2210 1480 2280 1510 A B
1780 1180 1860 1190 B B
2040 1350 2090 1370 A A
1620 1050 1630 1060 B A
1840 1250 1880 1250 A C
1560 1010 1620 1030 C B
1470 940 1500 960 B C
1370 890 1410 880 D B
1460 930 1490 920 C A
1250 790 1290 790 D A
1310 810 1360 840 C C
1090 690 1140 690 D C
HIGH / LOW HEAT CFM
40,000 INPUT - 3 Ton 60,000 INPUT - 3 Ton
JUMPER SETTINGS
CFM CFM
High Low High Low HEAT Tap ADJ Tap*
1045 740 1110 710 A Any
905 645 960 640 B Any
825 595 870 600 C Any
765 590 830 570 D Any
80,000 INPUT - 3 Ton 80,000 INPUT - 4 Ton
JUMPER SETTINGS
CFM CFM
High Low High Low HEAT Tap ADJ Tap*
1330 880 1490 990 A Any
1180 810 1350 900 B Any
1100 730 1220 820 C Any
1010 670 1120 770 D Any
100,000 INPUT - 5 Ton 120,000 INPUT - 5 Ton
JUMPER SETTINGS
CFM CFM
High Low High Low HEAT Tap ADJ Tap*
1880 1230 2150 1420 A Any
1670 1080 1930 1290 B Any
1530 980 1850 1190 C Any
1430 900 1660 1070 D Any
All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to 0.6” w.c. static pressure. From
0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c. external static pressure is not recommended.
NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower that what is required to operate an airflow switch on certain models of electronic air cleaners. Consult the
instructions for the electronic air cleaner for further details.
* The ADJ “D” tap should not be used.