13
YORK INTERNATIONAL
FORM 102.20-FA1 (1104)
FIG. 16 - REMOVE ELECTRICAL CONNECTORS
14. REMOVE SEAM CAPS FROM PANELS AT SHIP-
PING SPLITS
15. REMOVE LIGHT ASSEMBLY
a) Disconnect “stake-on” electrical connectors.
b) Remove wireway from where it fastens to top
panel(s).
FIG. 17 - REMOVE WIREWAY
c) Remove light assembly.
16. REMOVE TOP PANEL(S)
a) Prior to panel removal on tiered or vertical units
cut any gasket that crosses a seam. This will
prevent tearing gaskets.
b) Remove top panel(s).
17. REMOVE SIDE LOAD FILTER TRACKS OR FIL
TER BANK OF INDIVIDUAL FILTER FRAMES
a) Remove fi lter access panel(s).
b) Disconnect left and right vertical fi lter bulkheads
from top and bottom raceways.
c) Remove screws from bottom bulkhead under
fi lter assembly.
d) Move fi lter assembly away from coil.
e) Tip and remove fi lter assembly. Remove angle
fi lter assembly in two pieces.
18. REMOVE COIL
Leave control devices attached to the
coil if possible.
a) Remove screws connecting coil to bulkhead on
the air entering side.
FIG. 18 - REMOVE SCREWS SECURING COIL