251933-YTG-J-1009
Johnson Controls Unitary Products 75
060
(5.0)
208-1-60 26.2 134.0 41.0 2.3 7.6 0.0
None - - - 42.7 60
E05 4.0 1 19.2 66.7 80
E07 5.6 1 26.9 76.3 90
E10 8.0 1 38.5 90.7 100
E15 11.9 2 57.2 114.2 125
E20 15.9 2 76.4 138.2 150
E30 22.2 2 106.7 176.1 200
230-1-60 26.2 134.0 41.0 2.3 7.6 0.0
None - - - 42.7 60
E05 5.3 1 23.0 70.3 90
E07 7.5 1 32.6 81.7 100
E10 10.6 1 46.1 97.9 110
E15 15.9 2 69.1 125.5 150
E20 21.2 2 92.2 153.1 175
E30 29.6 2 128.7 196.8 200
208-3-60 15.6 110.0 24.4 2.3 7.6 0.0
None - - - 29.4 40
E05 4.0 1 11.1 43.3 50
E07 5.6 1 15.5 48.8 60
E10 8.0 1 22.2 57.2 60
E15 11.9 2 33.0 70.7 80
E20 15.9 2 44.1 84.6 90
E30 22.2 2 61.6 106.4 110
230-3-60 15.6 110.0 24.4 2.3 7.6 0.0
None - - - 29.4 40
E05 5.3 1 13.3 45.3 50
E07 7.5 1 18.8 52.0 60
E10 10.6 1 26.6 61.3 70
E15 15.9 2 39.9 77.2 80
E20 21.2 2 53.2 93.1 100
E30 29.6 2 74.3 118.4 125
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
XP036-060 (Direct Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps