Unit Dimensions (Cont'd)
YCAL0019 SI
NOTE: All dimensions are in mm unless specied otherwise.
LEFT END
171
100
BOTTOM OF PANEL
22 TYP.
VIEW B-B
POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK
1170
1149
295
51 DIA
(2) 76 X 38
RIGGING HOLES
BOTH ENDS
1126
BASE WIDTH
477
280
TO ACCESS PANEL 412
211
325
211
325
B
B
51 ANSI/AWWA C-606
CONN (typ)
IN
OUT
LD18689
NOTE:
Placement on a level surface free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and east of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airow
patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall - 2m;
rear to wall - 2m; cooler end to wall - 1.2m; coil end to wall - 2m; top - no obstructions allowed; distance between adjacent units - 3m. No
more than one adjacent wall may be higher than the unit. 1" nominal deection isolators (not shown) will increase overall unit height by 152.