49
YORK INTERNATIONAL
FORM 201.19-NM8 (804)
7
OPERATING LIMITATIONS AND SOUND POWER DATA
OPERATING LIMITATIONS – SI UNITS
* Maximum Ambient w/ High Ambient Kit is 54°C.
MIN MAX
LEAVING CHILLED LIQUID TEMP ( °C) 4.5 15
CHILLED WATER TEMP DIFFERENCE ( °C) 3 10
WATER SIDE PRESSURE (BAR) – 10
REFRIGERANT SIDE PRESSURE (BAR) – 20
COOLER FLOW
MODEL LITERS/SECOND
YCAS MIN. MAX.
0685EB 18.5 67.6
0775EB 21.0 76.0
0835EB 21.0 76.0
0905EB 21.0 76.0
0965EB 21.0 76.0
1065EB 27.2 101.0
1135EB 27.2 101.0
1215EB 27.2 101.0
AIR STANDARD FANS –18 46
ENTERING HIGH PRESS. FANS –18 46
CONDENSER (°C) LOW NOISE FANS –18 46
FAN STANDARD FANS 20
AVAILABLE STATIC HIGH PRESS. FANS OPTION 1 85
PRESSURE (Pa) HIGH PRESS. FANS OPTION 2 150
LOW NOISE FANS 10
ELECTRICAL THREE PHASE 50 Hz (V)
SOUND DATA (DBA)
MODEL
STD FAN
6-POLE
MOTOR
LOW NOISE
FAN
8-POLE
MOTOR
LOW NOISE FAN
8-POLE MOTOR
W/COMPRESSOR
BLANKET
LOW NOISE FAN
8-POLE MOTOR
W/ PERIMETER KIT
(DISCHARGE LINE WRAPPED)
LOW NOISE FAN
8-POLE MOTOR
W/COMPRESSOR
BLANKET & PERIMETER KIT
(DISCHARGE LINE WRAPPED)
0685EB 107 105 104 100 99
0775EB 108 106 105 101 100
0835EB 108 106 105 102 101
0905EB 108 106 105 103 102
0965EB 109 107 106 102 101
1065EB 110 108 107 102 101
1135SB 1-0 107 106 103 102
1215EB 110 108 107 103 102