EasyManua.ls Logo

York YCAS0130 - TABLE 6 - YCAS Style G, Across the Line Start

York YCAS0130
204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
180
YORK INTERNATIONAL
FORM 201.19-NM1 (204)
Micro Panel Contents
TABLE 6 – YCAS STYLE G, ACROSS THE LINE START - 60 HZ.
MODEL
NO.
VOLTAGE
CODE
CHILLER
NAMEPLATE
RLA
NO. OF
LEADS
PER PHASE
THRU CT.
100% FLA
OF SYSTEM
MP INPUT
VOLTAGE
130
17 246 *2 266 3.65
28 214 *2 231 3.2
40 130 2 140 3.89
46 107 1 116 3.2
58 86 1 93 2.58
140
17 267 *4 288 1.99
28 232 *2 251 3.49
40 140 2 151 4.2
46 116 1 125 3.49
58 93 1 100 2.78
150
SYS 1
17 295 *4 319 2.2
28 256 *4 276 1.91
40 155 2 167 4.64
46 128 2 138 3.84
58 103 1 111 3.09
150
SYS 2
17 265 *4 286 1.97
28 230 *2 248 3.44
40 139 2 150 4.18
46 115 1 124 3.44
58 92 1 99 2.75
160
17 295 *4 319 2.2
28 256 *4 276 1.91
40 155 2 167 4.64
46 128 2 138 3.84
58 103 1 111 3.09
170
SYS 1
17 321 *4 347 2.4
28 279 *4 301 2.09
40 169 *2 182 2.53
46 140 2 151 4.2
58 112 1 121 3.35
170
SYS 2
17 295 *4 319 2.2
28 256 *4 276 1.91
40 155 2 167 4.64
46 128 2 138 3.84
58 103 1 111 3.09
180
17 321 *4 347 2.4
28 279 *4 301 2.09
40 169 *2 182 2.53
46 140 2 151 4.2
58 112 1 121 3.35
* Indicates one lead/phase through motor protector.