TABLE 7 – YCAS STYLE G, WYE DELTA START - 60 HZ.
MODEL
NO.
VOLTAGE
CODE
CHILLER
NAMEPLATE
RLA
NO. OF
LEADS
PER PHASE
100% FLA
OF SYSTEM
MP SET
POINT
VOLTAGE
130
17 246 *4 266 2.13
28 214 *2 231 3.71
40 130 2 140 3.89
46 107 2 116 3.20
58 86 2 93 2.58
140
17 267 *4 288 2.31
28 232 *4 251 2.00
40 140 2 151 4.20
46 116 2 125 3.46
58 93 2 100 2.8
150
SYS 1
17 295 *4 319 2.56
28 256 *4 276 2.22
40 155 2 167 4.64
46 128 2 138 3.84
58 103 2 111 3.09
150
SYS 2
17 265 *4 286 2.31
28 230 *4 248 2.00
40 139 2 150 4.18
46 115 2 124 3.44
58 92 2 99 2.75
160
17 295 *4 319 2.56
28 256 *4 276 2.22
40 155 2 167 4.64
46 128 2 138 3.84
58 103 2 111 3.09
170
SYS 1
17 321 *4 347 2.8
28 279 *4 301 2.42
40 169 *2 182 2.93
46 140 2 151 4.20
58 112 2 121 3.35
170
SYS 2
17 295 *4 319 2.56
28 256 *4 276 2.22
40 155 2 167 4.64
46 128 2 138 3.84
58 103 2 111 3.09
180
17 321 *4 347 2.8
28 279 *4 301 2.42
40 169 *2 182 2.93
46 140 2 151 4.20
58 112 2 121 3.35
* Indicates one lead/phase through motor protector.