TABLE 1 – MOTOR PROTECTOR DIP SWITCH SETTING (CONT’D)
* Indicates one lead/phase through motor protector
2
YCAS STYLE G, ACROSS-THE-LINE – 60 HZ
MODEL
VOLT
CHILLER
NO.
MO TOR PROTECTOR
NO.
CODE
NAMEPLATE
LEADS
RLA
PER
MP
PHASE
DISPLAY
DIP SWITCH SETTINGS ON MP (“1” INDICATES ON)
HA XXX
128 64 32 16 8 4 2 1
17 321 *4 108 0 1 1 0 1 1 0 0
28 279 *4 94 0 1 0 1 1 1 1 0
180 40 169 *2 114 0 1 1 1 0 0 1 0
46 140 2 189 1 0 1 1 1 1 0 1
58 112 1 151 1 0 0 1 0 1 1 1
17 342 *4 115 0 1 1 1 0 1 0 0
28 298 *4 101 0 1 1 0 0 1 0 1
200 40 181 *2 122 0 1 1 1 1 1 1 0
46 149 2 201 1 1 0 0 1 0 0 1
58 119 1 161 1 0 1 0 0 0 0 1
17 374 *4 126 0 1 1 1 1 1 1 0
210
28 325 *4 110 0 1 1 0 1 1 1 0
SYS. 1
40 197 *2 133 1 0 0 0 0 1 0 1
46 163 *2 110 0 1 1 0 1 1 1 0
58 130 2 175 1 0 1 0 1 1 1 1
17 342 *4 115 0 1 1 1 0 1 0 0
210
28 298 *4 101 0 1 1 0 0 1 0 1
SYS. 2
40 181 *2 122 0 1 1 1 1 1 1 0
46 149 2 201 1 1 0 0 1 0 0 1
58 119 1 161 1 0 1 0 0 0 0 1
17 374 *4 126 0 1 1 1 1 1 1 0
28 325 *4 110 0 1 1 0 1 1 1 0
230 40 197 *2 133 1 0 0 0 0 1 0 1
46 163 *2 110 0 1 1 0 1 1 1 0
58 130 2 175 1 0 1 0 1 1 1 1