16 YORK INTERNATIONAL
FORM 201.18-NM1 (102)
Product Description
* Indicates one lead/phase through motor protector.
TABLE 1 – MOTOR PROTECTOR DIP SWITCH SETTING (CONT’D)
YCAS STYLE F, ACROSS-THE-LINE START – 60 HZ
MODEL VOLT
CHILLER
NO. MOTOR PROTECTOR
NO. CODE
NAMEPLATE
LEADS
MP OL
RLA
PER
VALUE
PHASE
SET
DIP SWITCH SETTINGS ON MP (“1” INDICATES ON)
128 64 32 16 8 4 2 1
0180
17321*41080110 1100
28279*494 0101 1110
40169*21140111 0010
46140 21891011 1101
58112 11511001 0111
0200
17342*41150111 0100
28298*41010110 0101
40181*21220111 1110
46149 22011100 1001
58119 11611010 0001
0210
17374*41260111 1110
SYS. 1
28325*41100110 1110
40197*21331000 0101
46163*21100110 1110
58130 21751010 1111
0210
17342*41150111 0100
SYS. 2
28298*41010110 0101
40181*21220111 1110
46149 22011100 1001
58119 11611010 0001
0230
17374*41260111 1110
28325*41100110 1110
40197*21331000 0101
46163*21100110 1110
58130 21751010 1111