17YORK INTERNATIONAL
FORM 201.18-NM1 (102)
TABLE 1 – MOTOR PROTECTOR DIP SWITCH SETTING (CONT’D)
YCAS STYLE F, WYE-DELTA START – 60 HZ
MODEL VOLT
CHILLER
NO. MOTOR PROTECTOR
NO. CODE
NAMEPLATE
LEADS
MP OL
RLA
PER
VALUE
PHASE
SET
DIP SWITCH SETTINGS ON MP (“1” INDICATES ON)
128 64 32 16 8 4 2 1
0130
17246*21931100 0001
28214*21671010 0111
40130 21751010 1111
46107 21441001 0000
5886 21160111 0100
0140
17267*41050110 1001
28232*491 0101 1011
40140 21891011 1101
46116 21571001 1101
5893 21260111 1110
0150
17295*41150111 0011
SYS. 1
28256*41000110 0100
40155 22091101 0001
46128 21731010 1101
58103 21391000 1011
0150
17265*41040110 1000
SYS 2.
28230*490 0101 1010
40139 21881011 1100
46115 21551001 1011
5892 21240111 1100
0170
17321*41261000 0010
SYS. 1
28279*41090110 1101
40169*21321000 0100
46140 21891011 1101
58112 21511001 0111
0170
17295*41150111 0011
SYS. 2
28256*41000110 0100
40155 22091101 0001
46128 21731010 1101
58103 21391000 1011
* Indicates one lead/phase through motor protector.