18 YORK INTERNATIONAL
FORM 201.18-NM1 (102)
Product Description
TABLE 1 – MOTOR PROTECTOR DIP SWITCH SETTING (CONT’D)
YCAS STYLE F, WYE-DELTA START – 60 HZ
MODEL VOLT
CHILLER
NO. MOTOR PROTECTOR
NO. CODE
NAMEPLATE
LEADS
MP OL
RLA
PER
VALUE
PHASE
SET
DIP SWITCH SETTINGS ON MP (“1” INDICATES ON)
128 64 32 16 8 4 2 1
0180
17321*41261000 0010
28279*41090110 1101
40169*21321000 0100
46140 21891011 1101
58112 21511001 0111
0200
17342*41341000 0110
28298*41170111 0101
40181*21421000 1110
46149 22011100 1001
58119 21611010 0001
0210
17374*41461001 0010
SYS. 1
28325*41270111 1111
40197*21541001 1010
46163*21281000 0000
58130 21751010 1111
0210
17342*41341000 0110
SYS. 2
28298*41170111 0101
40181*21421000 1110
46149 22011100 1001
58119 21611010 0001
0230
17374*41461001 0010
28325*41270111 1111
40197*21541001 1010
46163*21281000 0000
58130 21751010 1111
* Indicates one lead/phase through motor protector.