5
Operational limitations (English)
Voltage Limitations
The following voltage limitations are absolute and
operation beyond these limitations may cause serious
damage to the compressor.
Table 5 - Voltage Limitations
UNIT POWER MIN. MAX.
200-3-60 180 220
230-3-60 207 253
380/415-3-60 342 440
460-3-60 414 506
380/415-3-50 342 440
575-3-60 517 633
Section 5 – Technical data
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest Johnson Controls Oce for application requirements.
2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest Johnson Controls Oce for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
4. For operation at temperatures below 25°F (-3.9°C), the optional Low Ambient Kit will need to be installed
5. For operation at temperatures above 115°F (46.1°C), the optional High Ambient Kit will need to be installed on the system.
Excessive ow will cause damage to the
cooler. Do not exceed the maximum cooler
ow. Special care should be taken when
multiple chillers are fed by a single pump.